Check
Item
Operation
Check Standard
Troubleshooting
ALM
indicator
Steady on: A fault
alarm is generated.
Off: No fault alarm
is generated.
Refer to
ECC800 Data Center
Controller V100R001C30 User
Manual
to handle alarms, or contact
Huawei technical support.
RUN
indicator
Off: The power
supply is abnormal.
Blinking slowly:
The software runs
properly (the
indicator blinks at
0.5 Hz, on for 1s
and then off for 1s)
or registration with
the ECC800 is
successful.
Blinking at short
interval: The
communication is
interrupted or the
registration with the
ECC800 fails (the
indicator blinks at 4
Hz, on for 0.125s
and then off for
0.125s).
Blinking: The
indicator blinks at
super short intervals
for 0.5s (blinking at
10 Hz, on for 0.05s
and then off for
0.05s) and then
turns off for 0.5s.
The cycle lasts for
10s.
Check the power supply.
Refer to
ECC800 Data Center
Controller V100R001C30 User
Manual
to register the device, or