FusionModule1000A20 CT Solution
Maintenance Guide
3 Routine Maintenance
Issue 01 (2019-02-25)
Copyright © Huawei Technologies Co., Ltd.
18
Categ
ory
Mainten
ance
Item
Operation
Check
Standard
Troubleshooting
Camera
images
and
coverage
On the ECC800
WebUI, choose
System
Settings
>
Video
Settings
>
Video
Information
in
the monitoring
system, and you
can click
Access
Link
on the page
to access the
video link.
The video
images are
properly
displayed.
If no video image is
displayed:
1.
Connect the camera
cable again.
2.
If the cable is correctly
connected, replace the
camera by following
instructions in 5.3.5
Replacing a Camera.
The coverage of
the camera is
optimal.
If the camera coverage does
not meet the monitoring
requirement, adjust the
camera coverage.
Fire
extingu
ishing
system
VESDA
and its
power
supply
Check the
working status of
the VESDA and
its power supply.
The VESDA
and its power
supply are
normal.
If the VESDA or its power
supply is abnormal,
troubleshoot by following
instructions in documents
delivered with the VESDA.
3.4 Monthly Maintenance
3.4.1 Power Supply and Distribution System
Table 3-3
Monthly maintenance checklist for the power supply and distribution system
Maintena
nce Item
Operation
Check
Standard
Troubleshooting
PDC
Check the
luminance of the
indicators.
The
three-phase
power
indicators are
steady on.
If the indicator is off or dim, replace
it by following instructions in
5.1.2.5 Replacing an Indicator.
Check the SPD
indicator and SPD
circuit breaker
status.
The SPD
indicator is
green.
If the SPD indicator is red, replace
the SPD. For details, refer to 5.1.2.4
Replacing an SPD.
The SPD
circuit breaker
is switched to
ON.
Switch on the circuit breaker.