Figure 24 - Wiring Cascade System
Figure 25 - Cascade Termination Plug Detail
P. Cascade Master Pump and Sensor Wiring
1. Place the cascade master overlay sticker onto the field connection
board on the boiler designated as the cascade master.
2. Connect the system pump hot wire to the terminal marked SYS
PUMP.
3. Connect the system pump neutral to the BOILER NEUT terminal and
the pump ground wire to the BOILER GND terminal.
4. Connect a jumper wire from the 120 VOLT terminal to the SYS PUMP
PWR terminal.
5. Connect the boiler pump to the terminals marked BOILER HOT,
BOILER NEUT, and BOILER GND.
6. Connect the system pipe sensor to the terminals marked SYS
SENSOR.
7. Connect the outdoor sensor (if used) to the terminals marked
OUTDOOR SEN.
8. Connect the signal to start the system to the terminals marked
THERMOSTAT.
NOTE:
This signal can come from a room thermostat or a dry contact
closure. No power of any voltage should be fed into either of these
terminals.
NOTE:
Place the Cascade Master label (included in shipping envelope)
on top of the boiler designated Master.
Q. Cascade Follower Pump and Sensor Wiring
1. If it is desired to have the boiler control the boiler pump, connect
the boiler pump to the BOILER HOT, BOILER NEUT, and BOILER GND
terminals.
2. If you are using an indirect fired water tank connected directly to
the follower boiler, connect the pump for it to the DHW HOT, DHW
NEUT, and DHW GND terminals.
If desired, an alarm bell or light can be connected to the alarm
contacts of the follower boiler. The normally closed alarm contact
may be used to turn a device off if the boiler goes into lockout mode.
The alarm contacts are rated 5 amps at 120 VAC.
To connect an alarm device, connect the power for the device to
the ALARM COM terminal. Connect the alarm device hot wire to
the ALARM NO terminal. Connect the neutral or return of the alarm
device to the neutral or return of the power for the alarm device.
To connect a device that should be powered off during a boiler
lockout condition, follow the same instructions as above and use
the ALARM NC terminal rather than the ALARM NO terminal.
NOTE:
In a cascade system, the alarm output of the boiler addressed
as #1 will also be active if the master boiler has a lockout condition.
The alarm output of boilers addressed #2-7 will only sound if a
lockout condition occurs on that specific boiler.
Содержание MODCON500 FS
Страница 34: ...lp 445 r4 Rev 006 Rel 027 Date 7 21 20 34 Figure 26 Cascade Master and Follower Wiring ...
Страница 61: ...lp 445 r4 Rev 006 Rel 027 Date 7 21 20 61 Figure 34 Water Side Replacement Parts All Models ...
Страница 62: ...lp 445 r4 Rev 006 Rel 027 Date 7 21 20 62 Figure 35 Cabinet Replacement Parts All Models See Table ...
Страница 65: ...lp 445 r4 Rev 006 Rel 027 Date 7 21 20 65 Maintenance Notes ...