Failure of electric elements due to lime scale build-up on the heating surface, low pH, or other imbalance IS NOT
covered by the warranty.
C. Technical Specifications and Dimensions
Model
*Wattage (kW) Max Amperage
Required Breaker(s)
Required Wire Size
18kW
18
75
3 x 30A Double Pole
3 x 10 AWG w/ Ground
24kW
24
100
3 x 40A Double Pole
3 x 8 AWG w/ Ground
27kW
27
112.5
36kW
36
150
4 x 40A Double Pole
4 x 8 AWG w/ Ground
Technical Data
All Models
Minimum Water Flow to Activate
Unit
0.5 gpm
Working Pressure
7 - 150 psi (0.5 - 10 bar)
Tested Pressure
290 psi (20 bar)
Water Connections
3/4” NPT
Elements
18 - 27kW
2
36kW
3
Dimensions
18 - 27kW
20.7” (526 mm) Width x 13.3” (339 mm) Height x 4.5” (114 mm) Depth
36kW
25” (636 mm) Width x 13.3” (339 mm) Height x 4.5” (114 mm) Depth
Weight (Empty)
18 - 27kW
12.17 lb (5.52 kg)
36kW
16.23 lb (7.36 kg)
Temperature Range
86 - 122
o
F (30 - 50
o
C)
Table 3 - Technical Specifications - *Wattage based on maximum voltage.
Part 3 - Installation Instructions
A. Wall Mounting the Water Heater
1. Remove the two (2) screws attaching the water heater front cover. Remove the front cover. (Figure 1.)
• Do not install the unit above electrical boxes or junctions.
• The mounting surface must be solid and secure.
2. Position the unit on the mounting surface. Ensure the unit is level. Mount the unit to the wall with four (4)
screws of at least one (1) inch (25.4mm) in length at the marked points. See Figure 2.
Use screws suitable for the wall material and the weight of the water heater. Failure to do so could result in
property damages and damage to the water heater. Such damages ARE NOT covered by product warranty.
• The appliance must be mounted horizontally, with water inlets and outlets at the bottom. See Figure 3.
This water heater must be installed upright in the vertical position as described in this manual. DO NOT attempt
to install this water heater in any other orientation. Doing so will result in improper water heater operation and
property damage, and could result in serious personal injury or death.
Temperature Rise Δt (
o
F)
Flow Rate (GPM)
18kw
24kw
27kW
36kW
35
3.51
4.68
5.26
7.02
45
2.73
3.64
4.09
5.46
77
1.59
2.12
2.39
3.19
• Pull gently on the water heater to ensure that it is properly mounted.