Page 12
Electromagnetic Valve
Agent
Water flow displayer
Hydrant
Pressure
Temperature sensing cable
Manual call point
I/O module
Combined
Infrared
Heat
Photoelectric
Ion
Start: This refers to the address of the module needed to be started after the system gives an alarm.
Delay: This refers to the time delay after the control panel receives an alarm signal and before it makes
the module with the corresponding address act. The User can select among “000S”, “005S”, “010S”,
“030S”, “060S”, “090S”, “120S” and “150S” through
▲
and
▼
.
Note: After the setup is finished, press the # key to save the settings and to set the next group, or
press the * key to go back to the previous menu.
5) The user may move the cursor to the
Complex
option and press the # key for setting. The following
content will be displayed.
Complex integration is a kind of linkage in which the simultaneous alarming or feedback of two detectors
or modules in the system triggers module actions.
Group No.: This refers to the linkage number. There are 30 groups ranging from 01 to 30. Through this
option, the user can view, set or modify the linkage of the groups.
Register =1, valid; Register =0, invalid.
Addr 1:
This refers to the address of a alarm detector or alarm (feedback) module triggering the module
actions.
Addr 2: This refers to the address of a alarm detector or alarm (feedback) module triggering the module
actions.
Delay: This refers to the time delay after the control panel receives an alarm signal and before it makes
the module with the corresponding address act. The u
ser can select among “000S”, “005S”, “010S”,
“030S”, “060S”, “090S”, “120S” and “150S” through
▲
and
▼
.
Start: This refers to the address of the module needed to be started after the system gives an alarm.
When the two pieces of equipment corresponding to address 1 and address 2 give an alarm or make
feedback at the same time, module actions will occur after the set time delay is reached.
Note: After the setup is finished, press the # key to save the settings and to set the next group, or
press the * key to go back to the previous menu.
6) The user may move the cursor to the
Sounder
option and press the # key for setting. The following
content will be displayed.
Sounder integration is a kind of linkage in which a piece of monitoring equipment in a zone (including
Ion, Photoelectric, Heat, Infrared, Complex, Interface, Manual Alarm, temperature sensing cable,
Pressure, Hydrant, flow detector and so on) receives an alarm signal and starts the bell and the fire radio