Page 9
1) The User may set the
System integration
option by moving the cursor to the
System
option and
pressing the # key. The following content will be displayed.
The system integration is a kind of linkage in which a piece of monitoring equipment in the entire system
(including Ion, Photoelectric, Heat, Infrared, Complex, Interface, Manual Alarm, temperature sensing
cable, Pressure, Hydrant, flow detector and so on) may trigger module actions.
No.: This refers to the linkage number. There are 30 groups ranging from 01 to 30. Through this option,
the user can view, set or modify the linkage of the groups.
Register: Register =1, valid; Register =0, invalid.
Delay: This refers to the time delay after the control panel receives an alarm signal and before it makes
the module with the corresponding address act. The User can select among “000S”, “005S”, “010S”,
“030S”, “060S”, “090S”, “120S” and “150S” through
▲
and
▼
.
Address: This refers to the address of the module needed to be started by the system after an alarm is
given.
Note: After the setup is finished, press the # key to save, or the * key to go back to the previous
menu.
2) The User may move the cursor to the
Zone
option and press the # key for setting. The following
content will be displayed.
The zone integration is a kind of linkage in which a piece of monitoring equipment in a zone (including
Ion, Photoelectric, Heat, Infrared, Complex, Interface, Manual Alarm, temperature sensing cable.
Pressure, Hydrant, flow detector and so on) may trigger module actions.
Group No.: This refers to the linkage number. There are 30 groups ranging from 01 to 30. Through this
option, the user can view, set or modify the linkage of the groups.
Zone No.: There are 15 groups of zone numbers from 01 to 15.
Register: Register =1, valid; Register =0, invalid.
Delay: This refers to the time delay after the control panel receives an alarm signal and before it makes
the module with the corresponding address act. The User can select among “000S”, “005S”, “010S”,
“030S”, “060S”, “090S”, “120S” and “150S” through
▲
and
▼
.
Address: This refers to the address of the module needed to be started by the system after an alarm is
given.
Note: After the setup is finished, press the # key to save, or the * key to go back to the previous
menu.
3) The User may move the cursor to the
Floor integration
option and press the # key for setting. The
following content will be displayed.
The floor alarm integration is a kind of linkage in which a piece of monitoring equipment on a floor
(including Ion, Photoelectric, Heat, Infrared, Complex, Interface, Manual Alarm, temperature sensing
cable, Pressure, Hydrant, flow detector and so on) may trigger the module actions of the floor or the
floors close to it.