Environmental specifications
Specification
Value
—
Operating
10°C to 35°C (50°F to 95°F)
Non-operating
-30°C to 60°C (-22°F to 140°F)
Relative humidity (noncondensing)
—
Operating
8% to 90%
28°C (82.4°F), maximum wet bulb temperature
Non-operating
5% to 95%
38.7°C (101.7°F), maximum wet bulb temperature
All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 305 m (1.8°F per 1000 ft) to 3050 m (10,000 ft) is
applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). The upper limit and rate of change
might be limited by the type and number of options installed.
For certain approved hardware configurations, the supported system inlet temperature range is extended:
• 5°C to 10°C (41°F to 50°F) and 35°C to 40°C (95°F to 104°F) at sea level with an altitude derating of 1.0°C per every
175 m (1.8°F per every 574 ft) above 900 m (2953 ft) to a maximum of 3050 m (10,000 ft).
• 40°C to 45°C (104°F to 113°F) at sea level with an altitude derating of 1.0°C per every 125 m (1.8°F per every 410
ft) above 900 m (2953 ft) to a maximum of 3050 m (10,000 ft).
Mechanical specifications
Apollo DX2200 Gen10 Chassis
Specifications
Value
Dimensions
—
Height
8.76 cm (3.45 in)
Depth
87.93 cm (34.62 in)
Width
44.80 cm (17.64 in)
Weight (approximate values)
—
Weight (maximum)
41.16 kg (90.75 lb)
Weight (minimum)
13.10 kg (28.89 lb)