background image

attribute and how to disable WCE, see the

SCF Reference Manual for the Storage Subsystem

(G06.28+, H06.05+, J06.03+, L15.02+)

.

When the utility power is restored, you can enable WCE.

During a utility power failure, the system can continue to run until the data center UPS runs
out of power or until it shuts down.

88

UPS and Data Center Power Configurations

Содержание Integrity NonStop X NS7

Страница 1: ...HPE Integrity NonStop X NS7 Planning Guide Part Number 799257 004 Published June 2016 Edition L15 08 and subsequent L series RVUs ...

Страница 2: ...IT DialTone and The Open Group are trademarks of The Open Group in the U S and other countries Open Software Foundation OSF the OSF logo OSF 1 OSF Motif and Motif are trademarks of the Open Software Foundation Inc OSF MAKES NO WARRANTY OF ANY KIND WITH REGARD TO THE OSF MATERIAL PROVIDED HEREIN INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURP...

Страница 3: ...istribution Unit PDU Types for a Rack 24 AC Power Feeds in the Rack 38 AC Input Power for NS7 Racks 45 NS7 Enclosure Power Loads 48 Dimensions and Weights for NS7 AC Systems 50 Rack Stability for NS7 Systems 55 Environmental Specifications for NS7 AC Systems 55 Calculating Specifications for NS7 Enclosure Combinations 57 4 Managing NS7 System Resources 59 Planning Kernel Managed Swap KMS Space 59 ...

Страница 4: ...0 Cable Types and Connectors 80 B UPS and Data Center Power Configurations 81 Supported UPS Configurations 81 Non Supported UPS Configurations 85 C Warranty and regulatory information 93 Warranty information 93 Regulatory information 93 Index 96 4 Contents ...

Страница 5: ...ut UPS 40 16 Example of Top AC Power Feed in a Rack With Single Phase UPS 41 17 Example of Bottom AC Power Feed in a Rack With Single Phase UPS 42 18 Example of Top AC Power Feed in a Rack With Three Phase UPS 43 19 Example of Bottom AC Power Feed in a Rack With Three Phase UPS 44 20 NS7 System With a Fault Tolerant Data Center 82 21 NS7 System With a Rack Mounted UPS 83 22 SAS Disk Enclosures Wit...

Страница 6: ...n a replacement publication New and Changed Information in 799257 004 This version introduces the new HPE Integrity NonStop X NS7 X2 system HPE Integrity NonStop X NS7 Carrier Grade CG X2 system HPE NonStop X V2 Gen 9 CLIM HPE NonStop X FDR IB NonStop Application Direct Interface NSADI switch New and Changed Information in 799257 003R Updated Hewlett Packard Enterprise references Publishing Histor...

Страница 7: ...page 59 Kernel Managed Swap Facility 56 CLuster I O Modules CLIMs Storage IP or Telco Maximum CLIMs in a 16 CPU NonStop X system Minimum CLIMs for fault tolerance 2 Storage CLIMs 2 Networking CLIMs IP or Telco A Storage CLIM pair supports a maximum of 4 SAS disk enclosures Maximum SAS disk enclosures 100 per Storage CLIM pair Maximum SAS disk drives HPE LTO6 Tape Data Cartridge HPE NonStop BackBox...

Страница 8: ...Figure 1 Example NS7 System Configurations 42U and 36U 8 HPE Integrity NonStop X NS7 Systems ...

Страница 9: ...Stop BackBox VTR Tape support through Storage CLIMs 0 to 4 2 pairs Minimum maximum IO Expansion IB Switches HPE XP 7 Storage Array and HPE XP P9500 Storage Array ESS support through Storage CLIMs This file is required see Core Licensing page 9 Core licensing file Redundant configuration only Maintenance LAN 2 Minimum NonStop System Consoles for fault tolerance Supported with a maximum of 2 NSADI F...

Страница 10: ...Two Interconnect Ethernet switches that provide redundant Maintenance LAN connections for HSS bootcode download Two Interconnect InfiniBand switches that provide IB connectivity between processors and I O infrastructure An Intelligent Infrastructure that supports enhanced midplane signal integrity and compatibility with HPE Insight Control Two Onboard Administrator OA modules manage and monitor th...

Страница 11: ... server blade One HPE 10Gb dual port FlexibleLOM Ethernet Adapter One Infiniband FDR dual port Host Channel Adapter HCA Environment Monitoring Services to OA Disk bays and Smart Array Controller are not used More information Migrating NonStop X NS7 Systems service providers only CLuster I O Modules CLIMs NS7 systems support the Storage CLIM IP CLIM and Telco CLIM which function as I O or Ethernet ...

Страница 12: ...nd fabric connections 1 2 SAS HBA with two 6 Gbps SAS ports or FC HBA with two 8 Gbps FC ports must be ordered Optional order of SAS HBA with two 6 Gbps SAS ports or FC HBA with 8 Gbps FC ports 3 Gen9 Storage CLIM Characteristics of Gen9 Storage CLIM HBA in Slot IB HBA part of base configuration provides the InfiniBand fabric connections 1 2 SAS HBA with two 6 Gbps SAS ports or FC HBA with two 8 G...

Страница 13: ...prevent data loss on that volume is recommended The WRITECACHE enabled WCE option controls whether write caching is performed for disk writes More information UPS and Data Center Power Configurations page 81 Cable Types and Connectors page 80 IP CLIM and Telco CLIM The IP CLIM and Telco CLIM are sometimes referred to as Networking CLIMs These CLIMs function as 10 Gigabit Ethernet 10GbE adapters an...

Страница 14: ...mer port and Eth0 for maintenance support Slot 3 10GbE 2 port adapter for Eth2 and Eth1 customer ports FlexLOM Characteristics of Gen9 IP or Telco CLIM Interface InfiniBand interface card which provides the IB fabric connections Slot 1 10GbE 2 port adapter for Eth2 and Eth1 customer ports Slot 2 10GbE 2 port adapter for Eth4 and Eth3 customer ports Slot 3 1GbE 2 port adapter for Eth5 customer port...

Страница 15: ...e InfiniBand interface card which provides the IB fabric connections Slot 1 10GbE 2 port adapter for Eth1 and Eth2 customer ports Slot 2 10GbE 2 port adapter for Eth3 and Eth4 customer ports Slot 3 1GbE 2 port adapter for Eth5 customer port and Eth0 for maintenance support FlexLOM CLIM Cable Management Patch Panels The HPE CLIM uses two Cable Management patch panels for RJ45 and LC optical connect...

Страница 16: ...el IB system interconnect by providing a direct IB interconnect between NonStop Kernel NSK user space and external server based applications running on Linux More information NS7 System Installation Specifications page 24 NonStop Application Direct Interface NSADI Reference Manual Replacing a NonStop Blade IB Switch NonStop IO Expansion IB Switch or NonStop IB Cluster Switch in a NonStop X System ...

Страница 17: ...ail support see the OSM Configuration Guide Hewlett Packard Enterprise supports these rack mounted UPS modules Both support up to two HPE ERMs per UPS no mixing of UPS and ERM types UPS Manuals Supported UPS HPE UPS R5000 User Guide Single phase R5000 HPE UPS Network Module User Guide HPE 3 Phase UPS User Guide Three phase R12000 3 HPE UPS Management Module User Guide More information Power Specif...

Страница 18: ...paths connected to that switch If both the primary and the backup paths are connected to the same switch the LDEV goes down See the documentation that accompanies the ESS System Management Tools OSM Package The HPE Open System Management OSM product is the required system management tool for NonStop systems There are several new OSM tools and online help for managing the NS7 For more information o...

Страница 19: ...t Packet have your service provider copy the forms from the CLuster I O Module CLIM Installation and Configuration Manual L15 02 Component Location and Identification Each system resource is identified by a unique case sensitive ASCII resource name A name can range from one to a maximum of 64 characters The components in the system ship with preassigned naming conventions that you can change For m...

Страница 20: ...e minutes so they do not require connection to a site EPO switch EPO Requirement for R5000 UPS NOTE Two UPS are required for a single phase power configuration The rack mounted R5000 UPS is supported for a single phase power configuration Each UPS contains batteries has an EPO circuit and can be optionally installed in a rack For site EPO switches or relays consult your Hewlett Packard Enterprise ...

Страница 21: ...ice entrance to all system equipment This safety grounding system must comply with local codes and any other applicable regulations for the installation locale For proper grounding protective earth connection consult with your Hewlett Packard Enterprise site preparation specialist or power engineer Power Consumption The power consumption and inrush currents per connection can vary because of the u...

Страница 22: ...s For recommendations to keep the site as free of dust and pollution as possible consult with your heating ventilation and air conditioning HVAC engineer or your Hewlett Packard Enterprise site preparation specialist Zinc Particulates Over time fine whiskers of pure metal can form on electroplated zinc cadmium or tin surfaces such as aged raised flooring panels and supports If these whiskers are d...

Страница 23: ...lectrical outlets Airflow direction and current or future air conditioning ducts are not obstructed Eliminate any obstructions to equipment intake or exhaust air flow See Cooling and Humidity Control page 21 Adequate space planning to allow for future equipment Site layout plan includes provisions for things such as channels or fixtures used for cable routing cables patch panels and storage areas ...

Страница 24: ... the Intelligent rack using the HPE Rack Ground Bonding Kit BW891A ask your service provider to see the instructions in the HP Rack Options Installation Guide http www hpe com support Intelligent_Series_Rack_Manuals Power Distribution Unit PDU Types for a Rack The Enterprise series rack formerly known as the Intelligent rack supports Intelligent PDUs iPDUs and Modular PDUs Both PDU types use a cor...

Страница 25: ... with UPS 2 iPDUs without UPS page 29 Two PDU cores without UPS 2 iPDUs with single phase UPS page 30 Two PDU cores with UPS 2 iPDUs with three phase UPS page 31 4 mPDUs without UPS page 32 Four PDU cores without UPS Modular 4 mPDUs with single phase UPS page 33 Four PDU cores with UPS 4 mPDUs with three phase UPS page 34 2 mPDUs without UPS page 35 Two PDU cores without UPS 2 mPDUs with single ph...

Страница 26: ...illustration shows the power configuration for four iPDUs without UPS in a rack For detailed power specifications and connector types see Power Specifications page 45 Figure 2 Four iPDUs Without UPS NA JPN and INTL Single Phase and Three Phase 26 NS7 System Installation Specifications ...

Страница 27: ...on shows the power configuration for four iPDUs and two single phase UPS s in a rack For detailed power specifications and connector types see Power Specifications page 45 Figure 3 Four iPDUs With Single Phase UPS NA JPN and INTL Power Distribution Unit PDU Types for a Rack 27 ...

Страница 28: ...tration shows the power configuration for four iPDUs and a three phase UPS in a rack For detailed power specifications and connector types see Power Specifications page 45 Figure 4 Four iPDUs With Three Phase UPS NA JPN and INTL 28 NS7 System Installation Specifications ...

Страница 29: ...tration shows the connections for two iPDUs in a rack without a UPS For detailed power specifications and connector types see Power Specifications page 45 Figure 5 Two Intelligent PDUs Without UPS NA JPN and INTL Single Phase and Three Phase Power Distribution Unit PDU Types for a Rack 29 ...

Страница 30: ...tion shows the power configuration for two iPDUs and a single phase UPS in a rack For detailed power specifications and connector types see Power Specifications page 45 Figure 6 Two Intelligent PDUs With Single Phase NA JPN and INTL 30 NS7 System Installation Specifications ...

Страница 31: ...shows the power configuration for two iPDUs and a three phase UPS in a rack For detailed power specifications and connector types see Power Specifications page 45 Figure 7 Two Intelligent PDUs With Three Phase UPS NA JPN and INTL Power Distribution Unit PDU Types for a Rack 31 ...

Страница 32: ... shows the power configuration for four modular PDUs in a rack without a UPS For detailed power specifications and connector types see Power Specifications page 45 Figure 8 Four Modular PDUs Without UPS NA JPN and INTL Single Phase and Three Phase 32 NS7 System Installation Specifications ...

Страница 33: ...the power configuration for four modular PDUs and two single phase UPS s in a rack For detailed power specifications and connector types see Power Specifications page 45 Figure 9 Four Modular PDUs With Single Phase UPS NA JPN and INTL Power Distribution Unit PDU Types for a Rack 33 ...

Страница 34: ...hows the power configuration for four modular PDUs and a three phase UPS in a rack For detailed power specifications and connector types see Power Specifications page 45 Figure 10 Four Modular PDUs With Three Phase UPS NA JPN and INTL 34 NS7 System Installation Specifications ...

Страница 35: ...shows the power configuration for two modular PDUs without a UPS in a rack For detailed power specifications and connector types see Power Specifications page 45 Figure 11 Two Modular PDUs Without UPS NA JPN and INTL Single Phase and Three Phase Power Distribution Unit PDU Types for a Rack 35 ...

Страница 36: ...ration shows the connections for two modular PDUs with a single phase UPS in a rack For detailed power specifications and connector types see Power Specifications page 45 Figure 12 Two Modular PDUs With a Single Phase UPS NA JPN and INTL 36 NS7 System Installation Specifications ...

Страница 37: ...ion shows the connections for two modular PDUs with a three phase UPS in a rack For detailed power specifications and connector types see Power Specifications page 45 Figure 13 Two Modular PDUs With a Three Phase UPS NA JPN and INTL Power Distribution Unit PDU Types for a Rack 37 ...

Страница 38: ... With Single Phase UPS Example AC feed at top of rack with single phase UPS page 41 Example AC feed at the bottom of rack with single phase UPS page 42 With Three Phase UPS Example AC feed at top of rack with three phase UPS page 43 Example AC feed at the bottom of rack with three phase UPS page 44 NOTE The example power feed illustrations on the following pages show the connections to two PDUs an...

Страница 39: ...Figure 14 Example of Bottom AC Power Feed in a Rack Without UPS AC Power Feeds in the Rack 39 ...

Страница 40: ...Figure 15 Example of Top AC Power Feed in a Rack Without UPS 40 NS7 System Installation Specifications ...

Страница 41: ...Figure 16 Example of Top AC Power Feed in a Rack With Single Phase UPS AC Power Feeds in the Rack 41 ...

Страница 42: ...Figure 17 Example of Bottom AC Power Feed in a Rack With Single Phase UPS 42 NS7 System Installation Specifications ...

Страница 43: ...Figure 18 Example of Top AC Power Feed in a Rack With Three Phase UPS AC Power Feeds in the Rack 43 ...

Страница 44: ...Figure 19 Example of Bottom AC Power Feed in a Rack With Three Phase UPS Each PDU is wired to distribute the load segments to its receptacles 44 NS7 System Installation Specifications ...

Страница 45: ...s and regulations Select circuit breaker ratings according to local codes and any applicable regulations for the circuit capacity Note that circuit breaker ratings vary if your system includes an optional rack mounted UPS Table 3 North America Japan Single Phase Power Specifications Modular PDU 1 phase iPDU 1 phase R5000 1 phase UPS North America Japan 24 A 24 A 4500 W Output Load 200 240 V 200 20...

Страница 46: ...ctors 42 x C13 20 x C13 UPS outputs are connected to the compatible PDU inputs Notes Table 5 International Single Phase Power Specifications Modular PDU 1 phase iPDU 1 phase R5000 1 phase UPS International 32 A 32 A 4500 W Output Load 200 240 V 200 240 V 220 240 V Input Voltage IEC309 332P6 IEC309 332P6 IEC309 332P6 Input Connector N A N A 220 240 V Output Voltage 4x C19 6 x C19 1 x IEC309 332R6 O...

Страница 47: ...s 42 x C13 20 x C13 UPS outputs are connected to the compatible PDU inputs Notes Enclosure AC Input for NS7 Systems Enclosures IP CLIM SAS disk enclosure and so forth require Value Specification 200 208 220 230 240 V AC RMS Nominal input voltage 180 264 V AC Voltage range 50 or 60 Hz Nominal line frequency 47 53 Hz or 57 63 Hz Frequency ranges 1 Number of phases Single phase c7000 enclosures requi...

Страница 48: ... type of enclosure are Maximum Power Consumption VA 2 Typical Power Consumption VA 1 AC Power Lines per Enclosure Enclosure Type Products used by NS7 X1 AC systems 230 230 BL460c Gen8 CPU 64 GB RAM 260 260 BL460c Gen8 CPU 128 GB RAM 290 290 BL460c Gen8 CPU 192 GB RAM Products used by NS7 X2 AC systems 300 300 BL460c Gen9 CPU 64 GB RAM 315 315 BL460c Gen9 CPU 128 GB RAM 330 330 BL460c Gen9 CPU 192 ...

Страница 49: ...32GB Memory kit 125 75 2 D3700 SAS disk enclosure empty 6 6 400GB SSD 12G SAS SFF SC 7 4 300GB 15k rpm HDD 12G SAS SFF SC 15 9 1 Maintenance switch Ethernet 129 129 1 Rack mount system console 36 36 1 Console keyboard and monitor 145 135 1 Deskside system console 26 23 1 Deskside system Console monitor 1 Typical measured at 22C ambient temp 2 Maximum measured at 35C ambient temp NS7 Enclosure Powe...

Страница 50: ...eet 91 4 centimeters Unit Sizes for NS7 Systems Height U Enclosure Type 42 or 36 Rack 10 c7000 enclosure 2 CLIMs 2 SAS disk enclosures 1 CLIM patch panel RJ45 and Fiber 1 FDR IB ADI switch 1 FDR IB managed switch expansion 1 IB FDR managed switch IB cluster 1 Maintenance switch Ethernet 3 R5000 UPS single phase power 3 ERM for single phase UPS 6 R12000 3 UPS three phase power 3 ERM for three phase...

Страница 51: ...Systems Weight Depth Width Height Item cm in cm in cm in Depends on the 121 47 6 59 06 23 3 173 1 68 2 Rack 147 57 8 90 35 4 218 85 8 Shipping palletized enclosures installed See NS7 Rack and Enclosure Weights With Worksheet page 52 NS7 Enclosure Dimensions Depth Width Height Enclosure Type cm in cm in cm in 81 2 32 44 4 17 5 44 1 17 4 c7000 enclosure 1 phase 66 26 44 5 17 5 8 6 3 4 CLIMs all mode...

Страница 52: ...17 2 12 7 5 0 ERM for single phase power with R5000 UPS 36 5 14 4 66 26 26 1 10 3 R12000 3 UPS three phase power 66 26 43 8 17 2 13 1 5 1 ERM for three phase power NS7 Rack and Enclosure Weights With Worksheet The total weight of each rack is the sum the weights of the rack plus each enclosure installed in it Use this worksheet to determine the total weight Total Weight Number of Enclosures Enclos...

Страница 53: ...c Gen9 192GB RAM Storage Networking 24 55 Gen8 CLIM 20 45 Gen9 CLIM 17 38 SAS disk enclosure empty 45 1 400GB SSD 12G SAS SFF 2 5in SC 15 34 300GB 15k rpm HDD 12G SAS SFF 2 5 in SC 04 1 Disk blank 2 5 CLIM patch panels 3 6 Maintenance switch Ethernet 9 21 IB switches IB FDR managed switch expansion IB cluster switch IB ADI switch Manageability 8 18 Rack mounted system console 5 10 Keyboard and dis...

Страница 54: ...in a rack 12 27 NOTE One iPDU core weights 27 lbs A 4 iPDU core configuration would weigh 172 lbs 108 lbs for iPDU cores 64 lbs for extension bars Intelligent PDU core in a rack 1 8 Extension bar for Intelligent PDU in a rack 57 126 R5000 UPS single phase power 63 139 ERM single phase power 139 with batteries 307 with batteries R12000 3 UPS three phase power 60 without batteries 135 without batter...

Страница 55: ...ctions in the HP Rack Options Installation Guide http www hpe com support Intelligent_Series_Rack_Manuals Environmental Specifications for NS7 AC Systems NS7 Heat Dissipation Specifications and Worksheet Total BTU hour Unit Heat BTU hour Maximum Heat Dissipation Unit Heat BTU hour Typical Heat Dissipation Number Installed Enclosure Type 3856 2764 c7000 enclosure single phase 785 785 BL460c Gen8 se...

Страница 56: ...stem console and maintenance switch 9 F 5 C Repetitive 68 to 72 F 36 F 20 C Nonrepetitive 20 to 25 C 50 to 95 F 10 to 35 C Temperature c7000 CLIMs and SAS disk enclosures 1 8 F 1 C Repetitive 5 4 F 3 C Nonrepetitive 6 noncondensing 40 to 50 noncondensing 15 to 80 noncondensing Humidity all except c7000 enclosure 6 noncondensing 40 to 55 noncondensing 20 to 80 noncondensing Humidity c7000 enclosure...

Страница 57: ...lled with components the gaps between these components can cause adverse changes in the airflow negatively impacting cooling within the rack You must cover any gaps with blanking panels In high density environments air gaps in the enclosure and between adjacent enclosures should be sealed to prevent recirculation of hot air from the rear of the enclosure to the front NS7 Typical Acoustic Noise Emi...

Страница 58: ... 25 10 4 BL460c Gen8 Server Blade 2422 1535 710 450 17 38 3 47 2 D3700 SAS disk enclosure containing 25 HDDs with 300GB 6 GB SAS protocol per HDD 696 696 204 204 18 41 2 2 Rack mounted System Console 68 68 20 20 3 6 1 2 Maintenance switch 8 19 1 1 CLIM patch panel 153 338 42 1 Rack single phase 11998 9088 3514 2664 356 792 Total For a total thermal load for a system with multiple racks add the hea...

Страница 59: ...similar number of CPUs and application processes you can use the SWAP file usage on that system to help determine the SWAP file space for the new system You use the NonStop Kernel utility program NSKCOM to monitor configure and manage KMS files The information you obtain from NSKCOM and MEASURE is then used to adjust the swap file configuration More information Measure Reference Manual Kernel Mana...

Страница 60: ...e SAS enclosures attached to the same CLIM offset is the bay slot number of the disk in the SAS enclosure For an ESS disk the LUN number is calculated as base LUN offset base LUN is the base LUN number for the ESS port Its value can be 1000 2000 3000 4000 5000 6000 7000 8000 or 9000 and should be numbered sequentially for each of the ESS ports attached to the same CLIM offset is the LUN number of ...

Страница 61: ...le is preinstalled on new systems 36U Rack 2 to 16 processors configured in pairs Processors 64GB 128GB and 192GB memory configurations Memory See Planning Kernel Managed Swap KMS Space page 59 Kernel Managed Swap Facility Maximum CLIMs in a 16 CPU NS7 CG system 16 CLIMs without NSADI 15 CLIMs with NSADI Minimum CLIMs for fault tolerance 2 Storage CLIMs 2 Networking CLIMs IP or Telco A Storage CLI...

Страница 62: ...62 HPE Integrity NonStop X NS7 CG X2 System ...

Страница 63: ...lding port s of the equipment or subassembly is suitable for connection to intrabuilding or unexposed wiring or cabling only The intrabuilding port s of the equipment or subassembly MUST NOT be metallically connected to interfaces that connect to the OSP or its wiring These interfaces are designed for use as intrabuilding interfaces only Type 2 or Type 4 ports as described in GR 1089 CORE Issue 5 ...

Страница 64: ...ections between the chassis and the rack For connection and grounding instructions refer your service provider to the NonStop X System Hardware Installation Manual More information System Installation Specifications for NS7 CG Systems page 70 HPE BladeSystem c7000 Carrier Grade Enclosure Setup and Installation Guide service providers only NonStop X Server Blade for NS7 CG Systems The NS7 server bl...

Страница 65: ... and Telco CLIM CG The IP CLIM CG and Telco CLIM CG provide the same functionality and features as the IP CLIM and Telco CLIM including the RJ45 Cable Management Panel Notable differences are the carrier grade CLIMs have DC power supplies six fans and a ground connection between the CLIM chassis and the rack More information System Installation Specifications for NS7 CG Systems page 70 CLuster I O...

Страница 66: ...ch CG provides the communication network between system components NS7 CG systems use the GarrettCom Magnum 6K25 Fiber Switch with two DC power inputs 24 Ethernet ports labeled A1 through A8 B1 through B8 and C1 through C8 and a ground connection between the rack and the switch chassis More information NonStop X System Hardware Installation Manual System Installation Specifications for NS7 CG Syst...

Страница 67: ...G enclosure If the c7000 CG is not connected outputs 1 3 can be used for components with smaller breakers such as a CLIM 15A SAS disk enclosure 30A alarm panel 2A 4 maximum 50A rating outputs per power rail connect to other CG components CAUTION Outputs 4 7 are not rated for 80A breakers Do not install 80A breakers in these outputs Maximum 240A output load Nominal input voltage 48 60 VDC Operating...

Страница 68: ... rack and power cabling is accessed from the rear of the rack Fuses are configured by manufacturing per order specifications More information NonStop X System Hardware Installation Manual service providers only Fuse Panel Power Specifications for NS7 CG page 68 DC Power Distribution for NS7 CG Systems page 70 System Installation Specifications for NS7 CG Systems page 70 Fuse Panel Power Specificat...

Страница 69: ...rious disruption of service a malfunction or a FRU failure has occurred Immediate corrective action is required Major A non service affecting condition has occurred This alarm does not require immediate corrective action Minor A power fault has occurred Power No alarms are active Idle More information NonStop X System Hardware Installation Manual service providers only Technical Document System In...

Страница 70: ... NS7 CG systems DC Power Distribution for NS7 CG Systems Examples of NS7 CG Power Distributions Branch Circuit Protection Per Rail NS7 CG Component 3 x 80A c7000 CG enclosure 15A CLIM CG 30A CG SAS disk enclosure 2A CG Maintenance switch 2A Alarm panel 100A input rated Fuse panel 70 System Installation Specifications for NS7 CG Systems ...

Страница 71: ... Rail NS7 CG Component 3 x 80A c7000 CG enclosure 15A CLIM CG 30A CG SAS disk enclosure 2A CG Maintenance switch 2A Alarm panel 100A input rated Fuse panel 300A input rated Breaker panel DC Power Distribution for NS7 CG Systems 71 ...

Страница 72: ...ower Consumption VA 2 Typical Power Consumption VA 1 Power Lines per Enclosure NS7 CG X2 Enclosure Type 2250 810 6 c7000 CG enclosure 300 300 BL460c Gen9 CG CPU 64 GB RAM 315 315 BL460c Gen9 CG CPU 128 GB RAM 330 330 BL460c Gen9 CG CPU 192 GB RAM 270 140 2 Gen9 Storage CLIM CG 265 135 2 Gen9 Networking CLIM CG 4C 1C IP or Telco 265 135 2 Gen9 Networking CLIM CG 3C 2F IP or Telco 234 207 2 FDR IB A...

Страница 73: ...from the top Maximum payload is 1200 lbs 544 kg Rack weight is 451 lbs 204 kg Packaging and pallet weight is 200 lbs 91 kg Service Clearance and Floor Space Requirements Recommended Minimum Measurement cm in cm in 130 51 2 91 4 36 Front appearance side clearance 130 51 2 91 4 36 Rear service side clearance 2 5 1 0 Space between racks 68 6 27 Rack pitch Unpacking area When moving the rack off the s...

Страница 74: ... 3 47 Breaker panel 66 0 26 without safety cover 22 9 9 43 2 17 4 32 1 7 CG Maintenance switch 74 4 29 3 43 2 17 4 32 1 7 System Alarm panel Rack and Enclosure Weights Worksheet for NS7 CG Systems The total weight of each rack is the sum the weight of the rack plus each enclosure installed in it All weights are approximate Use this worksheet in Rack Weight Worksheet page 74 to calculate the weight...

Страница 75: ...al Weight 1 Maximum payload weight for the 36U rack 1200 lbs 544 3 kg Environmental Specifications for NS7 CG Systems Heat Dissipation Specification and Worksheet for NS7 CG Systems Table 10 Heat Dissipation Worksheet for NS7 CG X2 Seismic Rack Heat Dissipation Worksheet for Rack Number ______ Total BTU hour Maximum Unit Heat BTU hour Typical Unit Heat BTU hour Number Installed Enclosure Type 34 1...

Страница 76: ...nel 3 Total Heat Btu hour 1 Assumes full load per side with breaker panel dissipating 210W per side 2 Breaker panel load is the total nominal current on both sides 3 Maximum value Assumes full load per side of 70W 4 Fuse panel load is the total nominal current on both sides Operating Temperature Humidity and Altitude Value Specification Temperature range 1 5 to 50 ºC ambient temperature Operating ...

Страница 77: ...Table 310 18 Requirements for Site Power or Ground Cables The customer must ensure the site power cables meet the ampacity requirements for a NEBS 50 C environment CAUTION Use Table 310 16 or Table 310 18 along with Table 310 15 B 2 a See Required Documentation page 77 to verify the site power input cables meet the ampacity requirements for a NEBS 50 C environment To ensure the site power input ca...

Страница 78: ...roduct documentation to identify the recommended software update method To download product updates go to either of the following Hewlett Packard Enterprise Support Center Get connected with updates page www hpe com support e updates Software Depot website www hpe com support softwaredepot To view and update your entitlements and to link your contracts and warranties with your profile go to the He...

Страница 79: ...ct your local service provider or go to the CSR website www hpe com support selfrepair Remote support Remote support is available with supported devices as part of your warranty or contractual support agreement It provides intelligent event diagnosis and automatic secure submission of hardware event notifications to Hewlett Packard Enterprise which will initiate a fast and accurate resolution base...

Страница 80: ...ument as described in Technical Document Connectors Cable Type Connection RJ 45 to RJ 45 Ethernet CAT6A Maintenance LAN connections RJ 45 ports on Networking CLIM to Patch Panel LC LC MMF OM4 Fiber Optic ports on Networking CLIM to Patch Panel Mini SAS to HD SAS SAS copper Gen8 Storage CLIM to D3700 SAS disk enclosure SFF 8644 HD to SFF 8644 HD SAS copper Gen9 Storage CLIM to D3700 SAS disk enclos...

Страница 81: ...dware but these configurations are supported on all NonStop platforms and can be used with single phase and three phase UPS IMPORTANT You must change the ride through time for a Hewlett Packard Enterprise supported UPS from the manufacturing default setting to an appropriate value for your system During installation of an NS7 or HPE UPS your service provider can refer to the Setting the Ride Throu...

Страница 82: ...ations Define Site Infrastructure White Paper IMPORTANT With this configuration you can guarantee the data center never loses power Figure 20 shows an example of a NS7 system in a fault tolerant data center which has two simultaneously active power distribution paths with multiple backup UPS and engine generator systems Figure 20 NS7 System With a Fault Tolerant Data Center 82 UPS and Data Center ...

Страница 83: ...nning of the configured ride through time period OSM monitors if AC power is restored before the ride through period ends If AC Power is restored before the ride through period ends the ride through countdown terminates and OSM does not take further steps to prepare for an outage If AC Power is not restored before the ride through periods ends OSM broadcasts a PFAIL_SHOUT command to all processors...

Страница 84: ...e 22 SAS Disk Enclosures With a Rack Mounted UPS When the utility power fails the NS7 system powers off without an OSM initiated controlled shutdown of the I O operations and processors Only the products in the rack with the rack mounted UPS remain powered on All completed disk write transactions data are written to the disk drive media or the disk drive write cache The rack mounted UPS provides t...

Страница 85: ...e NS7 system do not use any of these non supported UPS configurations They might result in data loss NS7 System With a Data Center UPS Single Power Rail page 86 NS7 System With Data Center UPS Both Power Rails page 87 NS7 System With Rack Mounted UPS and Data Center UPS in Parallel page 89 NS7 System With Two Rack Mounted UPS in Parallel page 90 NS7 System With Cascading Rack Mounted UPS and Data ...

Страница 86: ... of the I O operations and processors If the utility power is not restored before the data center UPS shuts down any data in the NonStop X system disk drive write cache that has not been transferred to the disk drive media is lost To prevent data loss during a utility power failure you must manually disable the Write Cache Enable WCE option on all the disk drive volumes For information on the WRIT...

Страница 87: ...ation OSM does not manage or monitor the data center UPS Figure 24 NS7 System With Data Center UPS Both Power Rails When the utility power fails OSM does not detect that the data center UPS is running on battery and the UPS has entered its battery runtime OSM does not initiate the controlled shutdown of the I O operations and processors If the utility power is not restored before the data center U...

Страница 88: ...Storage Subsystem G06 28 H06 05 J06 03 L15 02 When the utility power is restored you can enable WCE During a utility power failure the system can continue to run until the data center UPS runs out of power or until it shuts down 88 UPS and Data Center Power Configurations ...

Страница 89: ... has entered its battery runtime OSM does not initiate the controlled shutdown of the I O operations and processors The rack mounted UPS shuts down before the data center UPS If the utility power is not restored before the data center UPS shuts down any data in the NS7 system disk drive write cache that has not been transferred to the disk drive media is lost To prevent data loss during a utility ...

Страница 90: ...lel OSM has the capability to monitor both UPSs but it does not have the logic to initiate the controlled shutdown of the I O operations and processors when utility power fails in this configuration If the utility power is not restored before both rack mounted UPSs shut down any data in the NS7 system disk drive write cache that has not been transferred to the disk drive media is lost If you want ...

Страница 91: ...he other A typical scenario where this behavior occurs is the failure of the smaller downstream UPS to recognize a stable input from its upstream source In the event of an upstream UPS failure or output disturbance the downstream UPS switches the load to battery Once the upstream UPS regains full function the downstream UPS should recognize a stable input and switch to pass through mode but this d...

Страница 92: ...r from the upstream UPS Factors can include the other types of loads which are driven by the upstream UPS Some non linear loads such as lighting or larger motors are more likely to distort the upstream UPS output than other electronic equipment The occurrence of these problems is unpredictable and has affected NonStop customers There is currently no known method to analytically predict the occurre...

Страница 93: ...w hpe com support Safety Compliance EnterpriseProducts Warranty information HPE ProLiant and x86 Servers and Options www hpe com support ProLiantServers Warranties HPE Enterprise Servers www hpe com support EnterpriseServers Warranties HPE Storage Products www hpe com support Storage Warranties HPE Networking Products www hpe com support Networking Warranties Regulatory information Warranty inform...

Страница 94: ...any 3000 Hanover Street Palo Alto CA 94304 U S Local representative information Russian Russia Belarus Kazakhstan Local representative information Kazakh Russia Belarus Kazakhstan Manufacturing date The manufacturing date is defined by the serial number CCSYWWZZZZ serial number format for this product 94 Warranty and regulatory information ...

Страница 95: ... 2002 and 38 for the week of September 9 In addition 2010 is indicated by 0 2011 by 1 2012 by 2 2013 by 3 and so forth YYWW where YY indicates the year using a base year of 2000 for example 0238 02 for 2002 and 38 for the week of September 9 Turkey RoHS material content declaration Ukraine RoHS material content declaration Regulatory information 95 ...

Страница 96: ...ion providing feedback on 79 Dust and microscopic particles 22 E EAC marking Belarus Kazakhstan Russia 94 Electrical disturbances 21 Electrical power loading 48 72 Electrostatic immunity tested 57 Emergency power off EPO switches 20 HPE R12000 3 UPS 20 HPE R5000 UPS 20 Empty slots see Blanking panels Enclosure dimensions 51 height in U 50 weight 52 Enterprise Storage System ESS and DC power 66 des...

Страница 97: ...re bay locations 13 front view 13 LUN 60 overview 13 Seismic rack specifications 73 Service clearances rack 50 Site power cables reference documentation 77 requirements 77 Specifications 36U rack 51 42U rack 51 enclosure dimensions 51 environmental 75 heat 55 nonoperating temperature humidity altitude 57 operating temperature humidity altitude 56 rack 73 Standard operating procedures ESD label 63 ...

Отзывы: