Maximum Power
Consumption (VA)
2
Typical Power
Consumption (VA)
1
Power Lines per Enclosure
NS7 CG X2 Enclosure Type
145
135
1
Deskside system console
26
23
1
Deskside system Console
monitor
1
Typical = measured at 22C ambient temp
2
Maximum = measured at 35C ambient temp
Dimensions and Weights of NS7 CG Systems
Seismic Rack Specifications for NS7 CG Systems
All information for connecting, grounding and installing an NS7 CG system is available to your
authorized service provider.
36U Seismic Rack Specification for NS7 CG Systems
71.4 in H x 26.7 in W x 39.4 in D
181.3 cm H x 67.8 cm W x 100 cm D
Cable entry is from the top
Maximum payload is 1200 lbs (544 kg)
Rack weight is 451 lbs ( 204 kg)
Packaging and pallet weight is 200 lbs (91 kg)
Service Clearance and Floor Space Requirements
Recommended
Minimum
Measurement
cm
in
cm
in
130
51.2
91.4
36
Front (appearance side) clearance
130
51.2
91.4
36
Rear (service side) clearance
< 2.5
< 1.0
--
--
Space between racks
68.6
27
--
--
Rack pitch
Unpacking area: When moving the rack off the shipping pallet, you need approximately 9 feet
(2.74 meters) on one side of the rack to allow you to slide the pallet out from under the rack after
the rack has been raised on the casters.
Unit Sizes for NS7 CG Systems
Height (U)
Enclosure Type
2
Fuse Panel
2
Breaker panel
1
System alarm panel
11 (includes seismic brace)
c7000 CG enclosure
2
CLIMs CG
1
CLIM CG Patch Panel
Dimensions and Weights of NS7 CG Systems
73
Содержание Integrity NonStop X NS7
Страница 8: ...Figure 1 Example NS7 System Configurations 42U and 36U 8 HPE Integrity NonStop X NS7 Systems ...
Страница 39: ...Figure 14 Example of Bottom AC Power Feed in a Rack Without UPS AC Power Feeds in the Rack 39 ...
Страница 40: ...Figure 15 Example of Top AC Power Feed in a Rack Without UPS 40 NS7 System Installation Specifications ...
Страница 41: ...Figure 16 Example of Top AC Power Feed in a Rack With Single Phase UPS AC Power Feeds in the Rack 41 ...
Страница 43: ...Figure 18 Example of Top AC Power Feed in a Rack With Three Phase UPS AC Power Feeds in the Rack 43 ...
Страница 62: ...62 HPE Integrity NonStop X NS7 CG X2 System ...