NS7 System With a Rack-Mounted UPS
shows an example of a supported configuration in a NS7 system with the left PDUs
connected to one or more rack-mounted UPS and the right PDUs connected directly to the utility
power. The rack-mounted UPS is connected to the utility power.
Figure 21 NS7 System With a Rack-Mounted UPS
When OSM detects that one power rail is running on UPS and the other power rail has lost power,
OSM logs an event indicating the beginning of the configured ride-through time period. OSM
monitors if AC power is restored before the ride-through period ends.
•
If AC Power is restored before the ride-through period ends, the ride-through countdown
terminates and OSM does not take further steps to prepare for an outage.
•
If AC Power is not restored before the ride-through periods ends, OSM broadcasts a
PFAIL_SHOUT
command to all processors (the processor running OSM being the last one
in the queue) to shut down the system ServerNet routers and processors. The
PFAIL_SHOUT
command enables disk writes for data that is in transit through controllers and disks to
complete.
Supported UPS Configurations
83
Содержание Integrity NonStop X NS7
Страница 8: ...Figure 1 Example NS7 System Configurations 42U and 36U 8 HPE Integrity NonStop X NS7 Systems ...
Страница 39: ...Figure 14 Example of Bottom AC Power Feed in a Rack Without UPS AC Power Feeds in the Rack 39 ...
Страница 40: ...Figure 15 Example of Top AC Power Feed in a Rack Without UPS 40 NS7 System Installation Specifications ...
Страница 41: ...Figure 16 Example of Top AC Power Feed in a Rack With Single Phase UPS AC Power Feeds in the Rack 41 ...
Страница 43: ...Figure 18 Example of Top AC Power Feed in a Rack With Three Phase UPS AC Power Feeds in the Rack 43 ...
Страница 62: ...62 HPE Integrity NonStop X NS7 CG X2 System ...