Table 9 Rack Weight Worksheet (continued)
Weight Worksheet for Rack Number _____
Total
Weight
Number of
Enclosures
Enclosure Type
kg
lb
kg
lb
5
12
BL460c Gen9 CPU 128GB
5
12
BL460c Gen9 CPU 192GB
.45
1
BL460c DC, 32GB memory
kit, add-on
20.5
45
Gen9 CLIM CG
2.2
5
CLIM CG Patch Panel
21.3
47
24CG SAS disk enclosure
(empty)
.45
1
400GB SSD, 12G SAS,
SFF, 2.5in, CC
.45
1
300GB, 15k rpm HDD, 12G
SAS, SFF, 2.5in, CC
.04
.1
Disk blank
2.3
5
CG Maintenance switch
--
--
--
Total Payload
204
451
--
Seismic rack, 36U
1
--
--
--
Total Weight
1
Maximum payload weight for the 36U rack: 1200 lbs (544.3 kg).
Environmental Specifications for NS7 CG Systems
Heat Dissipation Specification and Worksheet for NS7 CG Systems
Table 10 Heat Dissipation Worksheet for NS7 CG X2 Seismic Rack
Heat Dissipation Worksheet for Rack Number ______
Total (BTU/hour)
Maximum Unit Heat
(BTU/hour)
Typical Unit Heat
(BTU/hour)
Number
Installed
Enclosure Type
34
17
Alarm Panel
7677
2764
CG c7000 enclosure
1024
1024
BL460c Gen9 server
blade, 64GB
1075
1075
BL460c Gen9 server
blade, 128GB
1126
1126
BL460c Gen9 server
blade, 192GB
24
24
BL460c Gen9 server
blade, memory kit
921
478
Gen9 Storage CLIM
CG
Environmental Specifications for NS7 CG Systems
75
Содержание Integrity NonStop X NS7
Страница 8: ...Figure 1 Example NS7 System Configurations 42U and 36U 8 HPE Integrity NonStop X NS7 Systems ...
Страница 39: ...Figure 14 Example of Bottom AC Power Feed in a Rack Without UPS AC Power Feeds in the Rack 39 ...
Страница 40: ...Figure 15 Example of Top AC Power Feed in a Rack Without UPS 40 NS7 System Installation Specifications ...
Страница 41: ...Figure 16 Example of Top AC Power Feed in a Rack With Single Phase UPS AC Power Feeds in the Rack 41 ...
Страница 43: ...Figure 18 Example of Top AC Power Feed in a Rack With Three Phase UPS AC Power Feeds in the Rack 43 ...
Страница 62: ...62 HPE Integrity NonStop X NS7 CG X2 System ...