Depth
Width
Height
Enclosure
Type
cm
in
cm
in
cm
in
60.9
15.07
42.7
17.11
4.3
1.7
Rack-mount
system
console
42.3
16.66
43.1
16.97
4.3
1.7
Keyboard and
display
14.2
5.6
44.5
17.5
4.1
1.6
Modular PDU
19.1
7.5
44.5
17.5
4.1
1.6
Intelligent
PDU
62.7
24.7
42.7
16.8
4.3
1.7
FDR IB
switches
IB expansion
switch
IB cluster
switch
IB ADI switch
74.4
29.3
43.7
17.2
12.7
5.0
R5000 UPS
(single-phase
power)
71.9
28.3
43.8
17.2
12.7
5.0
ERM for
single-phase
power with
R5000 UPS
36.5
14.4
66
26
26.1
10.3
R12000/3
UPS
(three-phase
power)
66
26
43.8
17.2
13.1
5.1
ERM for
three-phase
power
NS7 Rack and Enclosure Weights With Worksheet
The total weight of each rack is the sum the weights of the rack plus each enclosure installed in
it. Use this worksheet to determine the total weight:
Total
Weight
Number of
Enclosures
Enclosure Type
kg
lbs
kg
lbs
144
318
36U rack
Maximum
payload weight
for the 36U rack:
3000 lbs (1360
kg).
151
333
42U rack
Maximum
payload weight
for the 42U rack:
3000 lbs (1360
kg).
52
NS7 System Installation Specifications
Содержание Integrity NonStop X NS7
Страница 8: ...Figure 1 Example NS7 System Configurations 42U and 36U 8 HPE Integrity NonStop X NS7 Systems ...
Страница 39: ...Figure 14 Example of Bottom AC Power Feed in a Rack Without UPS AC Power Feeds in the Rack 39 ...
Страница 40: ...Figure 15 Example of Top AC Power Feed in a Rack Without UPS 40 NS7 System Installation Specifications ...
Страница 41: ...Figure 16 Example of Top AC Power Feed in a Rack With Single Phase UPS AC Power Feeds in the Rack 41 ...
Страница 43: ...Figure 18 Example of Top AC Power Feed in a Rack With Three Phase UPS AC Power Feeds in the Rack 43 ...
Страница 62: ...62 HPE Integrity NonStop X NS7 CG X2 System ...