Table 10 Heat Dissipation Worksheet for NS7 CG X2 Seismic Rack (continued)
Heat Dissipation Worksheet for Rack Number ______
Total (BTU/hour)
Maximum Unit Heat
(BTU/hour)
Typical Unit Heat
(BTU/hour)
Number
Installed
Enclosure Type
631
461
Gen9 10GbE
Networking CLIM
4C/1C
631
461
Gen9 10GbE
Networking CLIM
4F/1C
614
426
SAS disk enclosure,
empty
20
20
SAS 2.5 in disk drive
400 GB, 15k rpm
24
14
SAS 2.5 in disk drive
300 GB, 15k rpm
136
119
CG Maintenance
switch
Unit Heat (Btu/hour with
both lines powered)
Unit Heat (Btu/hour with
one line powered)
Number
Installed
Enclosure Type
1433
717 x (breaker panel load
/480)
2
Breaker Panel
1
478
239 x (fuse panel load
/160)
4
Fuse panel
3
--
--
--
Total Heat
(Btu/hour)
1
Assumes full load per side with breaker panel dissipating 210W per side
2
Breaker panel load is the total nominal current on both sides
3
Maximum value. Assumes full load per side of 70W.
4
Fuse panel load is the total nominal current on both sides
Operating Temperature, Humidity, and Altitude
Value
Specification
Temperature range
1
-5 to 50 ºC ambient temperature
Operating
-40 to 70 ºC
Non operating
Relative humidity (non-condensing)
2
5 to 90% relative humidity
Operating
5 to 93% relative humidity
Non operating
Altitude
Operating
40 ºC from sea level to 6,000 ft.
30 ºC from 6,000 ft. to 13,000 ft.
Earthquake Zone 4
Seismic resistance
1
Temperature ratings are shown for sea level. No direct sunlight allowed.
2
Storage maximum humidity of 93% is based on a maximum temperature of 40°C.
76
System Installation Specifications for NS7 CG Systems
Содержание Integrity NonStop X NS7
Страница 8: ...Figure 1 Example NS7 System Configurations 42U and 36U 8 HPE Integrity NonStop X NS7 Systems ...
Страница 39: ...Figure 14 Example of Bottom AC Power Feed in a Rack Without UPS AC Power Feeds in the Rack 39 ...
Страница 40: ...Figure 15 Example of Top AC Power Feed in a Rack Without UPS 40 NS7 System Installation Specifications ...
Страница 41: ...Figure 16 Example of Top AC Power Feed in a Rack With Single Phase UPS AC Power Feeds in the Rack 41 ...
Страница 43: ...Figure 18 Example of Top AC Power Feed in a Rack With Three Phase UPS AC Power Feeds in the Rack 43 ...
Страница 62: ...62 HPE Integrity NonStop X NS7 CG X2 System ...