62
Chapter 6
Power
Configuring a PowerTrust UPS on V-Class systems
Configuring a PowerTrust UPS on
V-Class systems
You can use SAM (Peripheral Devices) to modify the UPS configuration.
You can specify:
• The serial port(s) to be used for the UPS.
• Whether to activate or deactivate the automatic shutdown feature
entirely.
• The parameter
shutdown_delay_mins
(default = 1 minute). This
parameter specifies the number of minutes to wait before initiating
shutdown -h
following notification that ac power to the UPS is lost.
This interval allows the computer to continue operation through brief
electrical glitches.
NOTE
Consider increasing the value of
shutdown_delay_mins
if the site
commonly experiences momentary power interruptions greater than one
(1) minute for which recovery of power is expected.
• The parameter
shutdown_timeout_mins
. This parameter specifies
the number of minutes to monitor the
shutdown -h
operation before
initiating reboot with the halt option. In this way a reboot is executed
even if the shutdown process changes.
NOTE
Consider increasing the value of
shutdown_timeout_mins
if
shutdown
(1M) will take longer than 5 minutes (including the 60 second
delay by
shutdown
(1M) after notification of users).
Consider decreasing the value of
shutdown_timeout_mins
if
shutdown
(1M) will take less than 5 minutes; small systems can take
advantage of this.
For more information on UPS on HP-UX, see the man pages on
ups_mond
(1M) and
ups_conf
(4).
Содержание 9000 V-Class
Страница 4: ......
Страница 10: ...x List of Tables ...
Страница 12: ...xii List of Figures ...
Страница 26: ...12 Chapter1 Overview Shared memory ...
Страница 66: ...52 Chapter4 Firmware OBP and PDC HElp command ...
Страница 112: ...98 Chapter7 Recovering from failures Abnormal system shutdowns ...
Страница 116: ...102 Index X X tool menu 30 ...