30
4 213 893 / 01
MAINTENANCE
After cleaning, assemble in reverse order.
The entire gas way / gas route tightness check up (with
leak detection spray) is necessary after the assembly.
7.5
Function check
- Set the gas boiler according to chapter 5.4
- Check all gas boiler connections for leaks
-
Check the system pressure, replenish where necessary
(at least 1,5 bar)
- Bleed the gas boiler
- Complete the test record sheet
7.6
Emission measurement
To access the service operation menu, press ‘MODE’ and ‘+’.
Service operation, which is carried out in heating mode,
can be recognised by the fact that the current level alter-
nates with the characters ‘SEr’ in the display.
When this operation mode is accessed, the burner starts
up at 50 % capacity. The output can then be varied be-
tween 0 and 100 % using the ‘+’ and ‘-’ keys.
To exit this operation mode, press the ‘RESET’ key (or the
mode is automatically exited after 20 minutes).
Gas screw connection
Bolting
Burner plate
Fig. 15
Fig. 16
Fig. 17