11
4 213 893 / 01
TECHNICAL INFORMATION
3.5
Heating system control
Boiler control
Normally, the user does not need to set the basic controller.
All settings have been made by the installer or the manufacturer.
Display: temperature
Changing of
the values
Display: Mode
RESET
Fault-clearance (display is
blinking, if there is a failure)
Saving of
the settings
Options, to change settings
(Parmeter)
(p.ex. Calorifier temperature)
ON/OFF
Manometer
Function options
(stepwise display option)
Function
Mode indication
Parameter Indication
Value indication
Meaning, Description
Standby-Mode
Normal position,
Start position
current flow temperature
no indication
0
= Standby, no heat demand, waiting time main gasvalve
1
= Rinsing
2
= Ignition
3
= Burner „on“ in heating operation
4
= Burner „on“ in hot water operation
5
= Air pressure deflector defectiv (no air pressure deflector in use)
6
= Burner „off“ in heating operation
(flow-Temp > flow-temp set point + blockage Offset ZH)
7
= Pump after-run time in heating operation
8
= Pump after-run time in hot water operation
9
= Burner „off“ on hot water operation
(flow-Temp > flow-temp. set point + Par.1 (2AB))
Fr
= Frost protection is activated
Su
= Summer short operation is activated