4 213 893 / 01
AUTOMATIC FIRING UNIT BIC 335-PARAMETER LIST
Parameter
Description
Unit
Level
Factory Setting
TG (16)
5/6-TG (35)
5/6-TG (45)
5/6-TG (60)
34
P2EB
fan decrement value
min
–1
/s
OEM
5(00)
35
P2EC
maximum fan speed
min
–1
OEM
60(00)
58(00)
59(00)
58(00)
36
P2ED
fan speed – second phase of pre-ventilation
min
–1
OEM
30(00)
29(00)
29(00)
29(00)
37
P2EE
fan speed following false start
min
–1
OEM
60(00)
58(00)
59(00)
58(00)
38
P2EF
fan speed following normal shutdown or blocking condition
min
–1
OEM
14(00)
13(00)
16(00)
13(00)
39
P2EG
fan speed in the first pre-ventilation phase
min
–1
OEM
60(00)
58(00)
59(00)
58(00)
40
P2EH
minimum fan speed
min
–1
OEM
14(00)
13(00)
16(00)
13(00)
41
P2EI
starting fan speed
min
–1
OEM
30(00)
29(00)
29(00)
29(00)
42
P2EJ
fan speed following a locking condition
min
–1
OEM
60(00)
58(00)
59(00)
58(00)
43
P2EK
P-factor (fan)
min
–1
OEM
35(00)
44
P2EL
I-factor (fan)
1s
OEM
12
45
P2EM minimum PWM value
1%
OEM
5
Staged Modulation in Heating Operation Mode
46
P2FA
interval 1
1s
OEM
30
47
P2FB
maximum output during interval 1
1%
OEM
20
48
P2FC
interval 2
1s
OEM
30
49
P2FD
maximum output during interval 2
1%
OEM
36
50
P2FE
interval 3
1s
OEM
30
51
P2FF
maximum output during interval 3
1%
OEM
52
52
P2FG
interval 4
1s
OEM
30
53
P2FH
maximum output during interval 4
1%
OEM
68
54
P2FI
interval 5
1s
OEM
30
55
P2FJ
maximum output during interval 5
1%
OEM
83
Further settings
56
P2GA
malfunction relay: functionality configuration 0=open, 1=closed
OEM
1
57
P2GB
line voltage selection 0=L/L 1=L/N
OEM
1
58
P2GC
flue gas temperature blocking condition
1°C
OEM
100
59
P2GD
maximum difference between flow and return temperatures
1°C
OEM
20
30
30
30
60
P2GE waiting time after opening main gas valve or
activation of combustion chamber ventilator
1min
HF
0
61
P2GF
external main gas valve (possibly LPG valve)/
combustion chamber ventilator present 0=no
HF
1
62
P2GG DHW charging (switch / pump) 0=KKP+switch 1=only WW-pump
HF
0
1
1
1
63
P2GH pump – minimum PWM value
1%
HF
35
64
P2GI
pump – maximum PWM value
1%
HF
70
65
P2GJ
three-way valve inversion 0=no 1=yes
HF
1
Adaptation for Liquid Gas
35
P2EC
maximum fan speed
min
–1
OEM
64(00)
55(00)
57(00)
57(00)
36
P2ED
fan speed – second phase of pre-ventilation
min
–1
OEM
60(00)
32(00)
34(00)
34(00)
39
P2EG
fan speed in the first pre-ventilation phase
min
–1
OEM
64(00)
55(00)
57(00)
57(00)
40
P2EH
minimum fan speed
min
–1
OEM
19(00)
13(00)
16(00)
14(00)
41
P2EI
starting fan speed
min
–1
OEM
60(00)
32(00)
34(00)
34(00)