37
B. LED Lights and Audible Alarm Safeties
Beep occurs and red "POWER OK" LED turns on when control switch is moved to "ICE"
position.
Sequence
Green LEDs 1 through 4 turn on and sequence from initial startup as listed in the table
below. Order of green LEDs from the outer edge of control board is 1, 4, 3, 2.
Sequence Step
LED
Energized
Components
Time LEDs are On
Min.
Max.
1-Minute Fill Cycle
4
WV
Harvest Cycle
1, 4, 2
Comp, FM*, FMR, HGV, WV
1 minute
20 minutes
Harvest Pump Time
(harvest assist)
1, 3, 2
Comp, FM*, FMR, HGV, PM
0 seconds 50 seconds
Freeze Cycle
1
Comp, FM/FMR, PM, LLV
5 minutes
freeze timer
setting
Anti-Slush Control
1, 3
Comp, FM/FMR, LLV
If S5 dip switch 5 on,
PM off 10 sec. when
thermistor at 36°F (2.2°C)
Pump-Out Cycle
1, 4
†
, 3, 2 Comp, FM*, FMR, HGV, PM, WV
†
, DV
10 seconds 20 seconds
*FM energized if on K1 Connector Pin #9;
†
pump-out timer setting
Alarms
Type
Alarm
Notes
1
Beep
High Evaporator Temp.
(temperature > 127°F) (53°C)
Check for harvest problem (stuck HGV or relay), hot water
entering unit, stuck HM, or shorted thermistor.
2
Beep
Harvest Backup Timer
(harvest > 20 min. for two
cycles in a row)
Check thermistor (open), HGV not opening, TXV or LLV
leaking by, low charge, inefficient Comp, or WRV leaking
by.
3
Beep
Freeze Timer
(freeze > freeze timer setting
for two cycles in a row)
Check FS stuck closed (up), WV leaking by, HGV leaking
by, PM not pumping, TXV defective, LLV not opening, low
charge, HM not bypassing, or inefficient Comp.
LED Blink
Freeze-Time
Correction (CB-2A7664-02)
(maximum freeze time
differential exceeded)
Red POWER OK LED blinks.
After 3 freeze-time correction cycles in 36 hours, yellow
EXT HARVEST LED also blinks.
Fill out freeze-up checklist. See "II.J. Freeze-Up Check
List."
To reset above safeties, press "ALARM RESET" button with power supply on.
6
Low Voltage
(92Vac±5% or less)
Red LED turns off if voltage protection operates.
Control voltage safeties automatically reset when voltage
is corrected.
7
High Voltage
(147Vac±5% or more)
Legend:
CB
–control board;
Comp
–compressor;
FM
–fan motor;
FMR
–fan motor remote;
FS
–float switch;
HGV
–hot gas valve;
HM
–headmaster (C.P.R.);
LLV
–liquid line
valve;
PM
–pump motor;
TXV
–thermostatic expansion valve;
WRV
–water regulating
valve;
WV
–inlet water valve