background image

69-0774B—1

4

T874D MULTISTAGE THERMOSTAT AND Q674A,D SUBBASES

M5632A

1.2 .8 .6

.3

.2

1.5

.4

50 60 70 80

HEAT

HEATING SET
POINT LEVER

50 60 70 80

COOL

COOLING SET
POINT LEVER

1.2

.8

.6

.3

.2

1.5

.4

.12

1.2

.4

.6

.3

.2

.15

.12

.1

0

.8

1.2

.4

.6

.3

.2

.15

.12

.8

.5

MOVE INDICATOR TO
MATCH CURRENT RATING
OF PRIMARY CONTROL

STAGE ONE
ANTICIPATOR
HEATING 
CONTROL

STAGE TWO
ANTICIPATOR
HEATING CONTROL

M5069

Fig. 8. Adjustable heat anticipator scales.

The current draw of each heating stage must be measured
with the thermostat removed and the power on to the
heating system.

1.

Connect an ac ammeter of appropriate range
between the heating terminals of the subbase:
Stage 1: between W1 and RH.
Stage 2: between W2 and RH.

2.

After one minute, read the ammeter and record the
reading.
Stage 1: __________ amperes.
Stage 2: __________ amperes.

3.

After mounting the thermostat, set the adjustable
heat anticipator to match the readings measured in
step 3.

NOTE:

If equipment cycles too fast, set the indicator to a
higher current rating, not more than one-half
division at a time, and recheck the cycle rate.
Most conventional two-stage heating equipment
is designed to operate at three cycles per hour
per stage and one-stage heating equipment at
six cycles per hour, at 50 percent load condition.

Temperature Setting

Move the heating and cooling setpoint levers to the
desired comfort positions. See Fig. 9. One lever control all
stages of heating, and the other lever controls all stages of
cooling. The minimum differential between the heating and
the cooling setpoint is 3

°

F (1.7

°

C), which means the

setting levers are made so they cannot be set closer
together than 3

°

F (1.7

°

C).

Fig. 9. Location of external components.

Subbase Setting

System switching positions control the system operation
as follows:

HEAT—heating system is automatically controlled by

the thermostat. Cooling system is off.

AUTO—thermostat automatically changes between

heat and cool modes, depending on indoor tempera-
ture.

COOL—cooling system is automatically controlled by

the thermosat. Heating system is off.

Fan switching positions control fan operation as follows:

ON—fan operates continuosly.
AUTO—fan operatres as controlled by the thermostat in

heat pump systems or conventional cooling mode;
fan operates as controlled by the plenum switch in
conventional heating mode.

To move subbase switches to the desired control posi-
tions, use thumb and index finger to slide the lever. The
lever must stop over desired function indicator position for
proper circuit operation.

CHECKOUT

Heating

Move the system switch on the Q674 Subbase to HEAT.
Move the setpoint lever on the T874 Thermostat about
10

°

F (6

°

C) above room temperature. Both stages of

heating and fan should start. Move the setpoint lever about
10

°

F (6

°

C) below room temperature. Heating and fan

should shut off.

NOTE:

To prevent compressor short cycling, some
manufacturer’s equipment includes a minimum
off timer to provide a 5-minute time delay before
turning the compressor on after the thermostat
last turned the compressor off, or after the
system first received power. This delay protects
the compressor.

Cooling

CAUTION

If outside air or heat exchange medium (water) is
below 50

°

F (10

°

C), do not operate cooling.

Move the system switch on the Q674 Subbase to COOL.
Move the setpoint lever on the T874 Thermostat about
10

°

F (6

°

C) below room temperature. Cooling and fan

should start (see NOTE above). Move the setpoint lever
about 10

°

F (6

°

C) above room temperature. Cooling and

fan should stop.

NOTE:

If using a Control Module Mark IV, there are time
delays built in. Check your Mark IV instructions
for details.

Fan

Move the fan switch to the ON position, the fan should run
continuously. When the fan switch is in the AUTO position,
fan operation is controlled by the heating or cooling
system.

Содержание Tradeline Q674A

Страница 1: ...re control to deviate from setpoint It is not a calibration problem CAUTION 1 Disconnect power supply to prevent electrical shock or equipment damage 2 To prevent interference with the thermostat linkage keep wire length to a minimum and run wires as close as possible to the subbase 3 Do not overtighten thermostat captive mounting screws because damage to subbase threads can result 4 Do not short ...

Страница 2: ... 2 Firmly tighten each terminal screw 3 Fit wires as close as possible to the subbase Push excess wire back into the hole 4 Plug hole with nonflammable insulation to prevent drafts from affecting the thermostat SPIRIT LEVEL MOUNTING HOLES 2 M927 TOP MOUNTING HOLES 2 WIRING TERMINAL THERMOSTAT CABLE OPENING TO SPRING FINGER CONTACTS ON THE THERMOSTAT UP TO 12 POST 2 FOR MOUNTING THERMOSTAT FOR STRA...

Страница 3: ...UMPER RC RH FOR SINGLE TRANSFORMER M5633 L1 HOT L2 1 COMPRESSOR CONTACTOR 2 COMPRESSOR CONTACTOR 1 H2 FALL C2 ANTICIPATOR RISE RISE C1 C2 THERMOSTAT SUBBASE SYSTEM COMPONENTS H2 ANTICIPATOR B NO FAN SWITCHING NO SYSTEM SWITCHING Fig 6 Schematic and hookup for T874D Thermostat and Q674A Subbase Fig 7 Mounting thermostat on subbase THERMOSTAT MOUNTING POST 2 M5631 50 60 70 80 50 60 70 80 HEAT COOL T...

Страница 4: ...s automatically controlled by the thermostat Cooling system is off AUTO thermostat automatically changes between heat and cool modes depending on indoor tempera ture COOL cooling system is automatically controlled by the thermosat Heating system is off Fan switching positions control fan operation as follows ON fan operates continuosly AUTO fan operatres as controlled by the thermostat in heat pum...

Страница 5: ...69 0774B 1 5 T874D MULTISTAGE THERMOSTAT AND Q674A D SUBBASES CALIBRATION Thermostat T874 Thermostats are accurately calibrated at the factory They do not have provision for field calibration ...

Страница 6: ... AND Q674A D SUBBASES Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 69 0774B 1 C B Rev 4 97 Home and Building Control Honeywell International Inc P O Box 524 Golden Valley MN 55422 ...

Страница 7: ...s Le fait de ne pas les suivre risque d endommager le produit ou de constituer un danger 2 Vérifier les caractéristiques nominales spécifiées dans les instructions et indiquées sur le produit pour s assurer que celui ci correspond à l application prévue 3 L installateur doit être un technicien d expérience ayant reçu une formation pertinente 4 Une fois l installation terminée vérifier le fonctionn...

Страница 8: ...st pas de niveau entraînera un écart entre la température ambiante et le point de consigne du thermostat Il ne s agit pas d un problème d étalonnage Thermostat multi étage T874D et plaques de commutation Q674A D MF925 ANNEAU D ADAPTATION PLAQUE DE COMMUTATION CACHE VIS DE FIXATION 2 VIS DE FIXATION 2 1 PLAQUE DE COMMUTATION VIS DE FIXATION 2 BOÎTE DE SORTIE HORIZONTALE 1 2 2 PIÈCE NON COMPRISE ACC...

Страница 9: ...le long de la bordure intérieure du haut du support du thermostat Ces ergots s insèrent dans les encoches de la plaque de commutation Installer le support du thermostat sur la plaque de commutation 5 Aligner les vis du support de thermostat sur les tiges de la plaque de commutation Voir Fig 7 Serrer les deux vis de fixation imperdables NE PAS TROP SERRER les vis pour éviter d endommager les tiges ...

Страница 10: ...tème de chauffage 1 Raccorder l ampèremètre c a avec la gamme de mesure appropriée entre les bornes de chauffage de la plaque de commutation Étage 1 ______entre W1 et RH Étage 2 ______entre W2 et RH TIGES DE FIXATION DU THERMOSTAT 2 MF5631 50 60 70 80 50 60 70 80 HEAT COOL TROUS DE FIXATION DU THERMOSTAT 2 PLAQUE DE COMMUTATION THERMOSTAT VIS DE FIXATION IMPERDABLES 2 2 Attendre une minute ensuite...

Страница 11: ...AT Placer le doigt de réglage du chauffage du thermostat T874 à environ 6 C 10 F au dessus de la température ambiante Les deux étages de chauffage et le ventilateur devraient se mettre en marche Placer le doigt de réglage du chauffage à environ 6 C 10 F au dessous de la température ambiante Le chauffage et le ventilateur devraient s arrêter REMARQUE Certains fabricants ajoutent une minuterie à leu...

Страница 12: ...D SUBBASES Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 69 0774B 1 C B Revu 4 97 Imprimé aux États Unis Home and Building Control Honeywell International Inc P O Box 524 Golden Valley MN 55422 ...

Отзывы: