background image

69-0774B—1

2

T874D MULTISTAGE THERMOSTAT AND Q674A,D SUBBASES

4.

Level the subbase using a spirit level. See Fig. 3,
and firmly tighten subbase mounting screws. The
subbase mounting holes provide for minor out-of-
level adjustments.

IMPORTANT

An incorrectly leveled subbase will cause the
temperature control to deviate from setpoint. It is
not a calibration problem.

M925

VERTICAL 
OUTLET
BOX

ADAPTER
RING

SUBBASE

COVER 
PLATE

MOUNTING
SCREWS (2)

MOUNTING
SCREWS (2)

1

SUBBASE

MOUNTING
SCREWS (2)

HORIZONTAL
OUTLET
BOX

1

2

2

NOT INCLUDED WITH UNIT.

ACCESSORY PARTS AVAILABLE (193121A).

1

2

Fig. 1. Installation of Q674 Subbase on outlet box.

WIRES THROUGH
WALL OPENING

WALL 

WALL
ANCHORS
(2)

SUBBASE

MOUNTING
SCREWS (2)

M926

MOUNTING
HOLES

Fig. 2. Installation of Q674 Subbase on wall.

Wiring the Subbase

All wiring must comply with local electrical codes and
ordinances. Follow equipment manufacturer’s wiring
instructions when available. To wire subbase, proceed as
follows:

1.

Connect the system wires to the subbase. See
Fig. 5 and 6. A letter code is located near each
terminal for identification. The terminal barrier
permits straight or conventional wraparound wiring
connection. See Fig. 4.

Fig. 3. Subbase components and leveling procedure.

2.

Firmly tighten each terminal screw.

3.

Fit wires as close as possible to the subbase. Push
excess wire back into the hole.

4.

Plug hole with nonflammable insulation to prevent
drafts from affecting the thermostat.

SPIRIT LEVEL

MOUNTING 
HOLES (2)

M927

TOP 
MOUNTING 
HOLES (2)

WIRING
TERMINAL

THERMOSTAT
CABLE OPENING

TO SPRING FINGER 
CONTACTS ON THE 
THERMOSTAT 
(UP TO 12)

POST (2) FOR
MOUNTING
THERMOSTAT 

FOR STRAIGHT
INSERTION–
STRIP 5/16 IN. (8 MM)

FOR WRAPAROUND–
STRIP 7/16 IN. (11 MM)

SUBBASE TERMINAL SCREW

M928

BARRIER

Fig. 4. Barrier configuration.

Mount Thermostat

1.

Remove the thermostat cover by pulling the bottom
edge of the cover upward until it snaps free of the
mounting slots.

NOTE:

The cover is hinged at the top and must be
removed by pulling up at the bottom.

2.

Carefully remove and discard the polystyrene
packing insert that protects the mercury switches
during shipment.

3.

Turn over thermostat base and note the spring
fingers that engage the subbase contacts. Make
sure the spring fingers are not bent flat, preventing
proper electrical contact with the subbase.

4.

Note the two tabs on the top inside edge of the
thermostat base. The tabs fit into corresponding
slots on top of the subbase. Mount the thermostat
on the subbase.

5.

Align the two captive mounting screws in the
thermostat base with the posts on the subbase. See
Fig. 7. Tighten both screws. Do not overtighten
screws or damage to subbase posts can result.

Содержание Tradeline Q674A

Страница 1: ...re control to deviate from setpoint It is not a calibration problem CAUTION 1 Disconnect power supply to prevent electrical shock or equipment damage 2 To prevent interference with the thermostat linkage keep wire length to a minimum and run wires as close as possible to the subbase 3 Do not overtighten thermostat captive mounting screws because damage to subbase threads can result 4 Do not short ...

Страница 2: ... 2 Firmly tighten each terminal screw 3 Fit wires as close as possible to the subbase Push excess wire back into the hole 4 Plug hole with nonflammable insulation to prevent drafts from affecting the thermostat SPIRIT LEVEL MOUNTING HOLES 2 M927 TOP MOUNTING HOLES 2 WIRING TERMINAL THERMOSTAT CABLE OPENING TO SPRING FINGER CONTACTS ON THE THERMOSTAT UP TO 12 POST 2 FOR MOUNTING THERMOSTAT FOR STRA...

Страница 3: ...UMPER RC RH FOR SINGLE TRANSFORMER M5633 L1 HOT L2 1 COMPRESSOR CONTACTOR 2 COMPRESSOR CONTACTOR 1 H2 FALL C2 ANTICIPATOR RISE RISE C1 C2 THERMOSTAT SUBBASE SYSTEM COMPONENTS H2 ANTICIPATOR B NO FAN SWITCHING NO SYSTEM SWITCHING Fig 6 Schematic and hookup for T874D Thermostat and Q674A Subbase Fig 7 Mounting thermostat on subbase THERMOSTAT MOUNTING POST 2 M5631 50 60 70 80 50 60 70 80 HEAT COOL T...

Страница 4: ...s automatically controlled by the thermostat Cooling system is off AUTO thermostat automatically changes between heat and cool modes depending on indoor tempera ture COOL cooling system is automatically controlled by the thermosat Heating system is off Fan switching positions control fan operation as follows ON fan operates continuosly AUTO fan operatres as controlled by the thermostat in heat pum...

Страница 5: ...69 0774B 1 5 T874D MULTISTAGE THERMOSTAT AND Q674A D SUBBASES CALIBRATION Thermostat T874 Thermostats are accurately calibrated at the factory They do not have provision for field calibration ...

Страница 6: ... AND Q674A D SUBBASES Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 69 0774B 1 C B Rev 4 97 Home and Building Control Honeywell International Inc P O Box 524 Golden Valley MN 55422 ...

Страница 7: ...s Le fait de ne pas les suivre risque d endommager le produit ou de constituer un danger 2 Vérifier les caractéristiques nominales spécifiées dans les instructions et indiquées sur le produit pour s assurer que celui ci correspond à l application prévue 3 L installateur doit être un technicien d expérience ayant reçu une formation pertinente 4 Une fois l installation terminée vérifier le fonctionn...

Страница 8: ...st pas de niveau entraînera un écart entre la température ambiante et le point de consigne du thermostat Il ne s agit pas d un problème d étalonnage Thermostat multi étage T874D et plaques de commutation Q674A D MF925 ANNEAU D ADAPTATION PLAQUE DE COMMUTATION CACHE VIS DE FIXATION 2 VIS DE FIXATION 2 1 PLAQUE DE COMMUTATION VIS DE FIXATION 2 BOÎTE DE SORTIE HORIZONTALE 1 2 2 PIÈCE NON COMPRISE ACC...

Страница 9: ...le long de la bordure intérieure du haut du support du thermostat Ces ergots s insèrent dans les encoches de la plaque de commutation Installer le support du thermostat sur la plaque de commutation 5 Aligner les vis du support de thermostat sur les tiges de la plaque de commutation Voir Fig 7 Serrer les deux vis de fixation imperdables NE PAS TROP SERRER les vis pour éviter d endommager les tiges ...

Страница 10: ...tème de chauffage 1 Raccorder l ampèremètre c a avec la gamme de mesure appropriée entre les bornes de chauffage de la plaque de commutation Étage 1 ______entre W1 et RH Étage 2 ______entre W2 et RH TIGES DE FIXATION DU THERMOSTAT 2 MF5631 50 60 70 80 50 60 70 80 HEAT COOL TROUS DE FIXATION DU THERMOSTAT 2 PLAQUE DE COMMUTATION THERMOSTAT VIS DE FIXATION IMPERDABLES 2 2 Attendre une minute ensuite...

Страница 11: ...AT Placer le doigt de réglage du chauffage du thermostat T874 à environ 6 C 10 F au dessus de la température ambiante Les deux étages de chauffage et le ventilateur devraient se mettre en marche Placer le doigt de réglage du chauffage à environ 6 C 10 F au dessous de la température ambiante Le chauffage et le ventilateur devraient s arrêter REMARQUE Certains fabricants ajoutent une minuterie à leu...

Страница 12: ...D SUBBASES Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 69 0774B 1 C B Revu 4 97 Imprimé aux États Unis Home and Building Control Honeywell International Inc P O Box 524 Golden Valley MN 55422 ...

Отзывы: