5
. Internal Memory
5.2. I/O area of TC module conversion data
70
Isolated Thermocouple Input Module TC4S User's Guide
R200
Honeywell
September 2010
Depending on the type of sensor and temperature metric system, it outputs temperature
conversion values within the following range.
Celsius(°)
Fahrenheit[°F]
K
-2600 ~ 13600
-4360 ~ 24800
J
-2100 ~ 12100
-3460 ~ 22100
E
-2600 ~ 10100
-4360 ~ 18500
T
-2600 ~ 4100
-4360 ~ 7700
B
3900 ~ 18100
7340 ~ 32900
R
- 600 ~ 17600
- 760 ~ 32000
S
- 600 ~ 17600
- 760 ~ 32000
N
-2800 ~ 13100
-4720 ~ 23900
C
- 100 ~ 23100
140 ~ 41900
ATTENTION
•
Output range of temperature conversion value is within ±10°C margin of
the maximum temperature range.
For instance, in case of type K sensor, it indicates
−
10°
of L
and
+10
°
of
H, -2600~13600.
•
The area is cleared if a channel stops (output 0 if it stops).
•
The temperature indication/settings in 2MLF-TC4S module displays
down to one decimal place (however, actually it does not display the
decimal point).
Channel scale operation value
1.
It outputs scale operation value for temperature conversion value to Address 8 ~11
(%UWa.b08~11) by channels.
RFERENCE - INTERNAL
For additional information, refer to Specifications.
2.
Scale operation value can be temporarily set as 16 bits data:
−
32768 ~ 32767 or 0 ~
65535.
Содержание TC4S
Страница 114: ...7 Troubleshooting 7 4 Error code 114 Isolated Thermocouple Input Module TC4S User s Guide R200 Honeywell September 2010 ...
Страница 126: ...8 Appendix 8 3 Dimension 126 Isolated Thermocouple Input Module TC4S User s Guide R200 Honeywell September 2010 ...
Страница 127: ...8 Appendix 8 3 Dimension R200 Isolated Thermocouple Input Module TC4S User s Guide 127 September 2010 Honeywell ...
Страница 128: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...