5
. Internal Memory
5.3. Operation parameter setting area
R200
Isolated Thermocouple Input Module TC4S User's Guide
77
September 2010
Honeywell
BIT
Description
0
Celsius
1
Fahrenheit
3.
The area shows the same results of temperature metric system assignment in the
I/O
parameter setting
window.
Filter value setting area (address 6~9); filter constant
1.
If filter value is set as 0, it does not process filtering the channel and instead, yields
temperature conversion value sampling process.
2.
If setting a value between 1 ~ 159 or over 64001, 0 (filter prohibited) is set
internally;
%UXa.b.24 ~ 27
(setting error flag) is ON (the bit, 1 of setting error
information area (address 60 ~ 63) would be ON).