5
. Internal Memory
5.1. Configuration of internal memory
R200
Isolated Thermocouple Input Module TC4S User's Guide
61
September 2010
Honeywell
Address
Variable Name
Description
R/W
Signal
Direction
%UXa.b.
470
_ab_CH2_ALMEN
CH2 Alarm(PVA/RCA)
Enable/Disable
%UXa.b.
471
_ab_CH3_ALMEN
CH3 Alarm(PVA/RCA)
Enable/Disable
R/W
%UXa.b.
472
_ab_CH0_RJCDS
CH0 RJC Enable/Disable
R/W
%UXa.b.
473
_ab_CH1_RJCDS
CH1 RJC Enable/Disable
R/W
%UXa.b.
474
_ab_CH2_RJCDS
CH2 RJC Enable/Disable
R/W
%UXa.b.
475
_ab_CH3_RJCDS
CH3 RJC Enable/Disable
CPU →
TC
ATTENTION
Typical addressing: The following is a typical example of the addressing in
the thermocouple input module. _ab_ in the variable/address refers to the
number of base and slots on which the module is configured.
For instance, in case reading or writing special module variable area, 4th bit
data of a module installed on #0 base and #4 slot, is expressed as follows:
R: Write only for the data for the module in MasterLogic 200 PLC.
R/W: MasterLogic 200 PLC can read and write an instruction to the module.
%U Address : The data that is usually read or written such as conversion
data of special module’s internal memory in PLC CPU, which is used to read
or write every time when scanning special area (regularly read data, defined
in module) of special/communication module in MasterLogic 200 PLC is
assigned in the area. As other devices, it is possible to directly use general
instructions such as MOV, CMP, ADD, and so on (on the other hand,
module’s parameter area requires PUT/GET instruction).
Содержание TC4S
Страница 114: ...7 Troubleshooting 7 4 Error code 114 Isolated Thermocouple Input Module TC4S User s Guide R200 Honeywell September 2010 ...
Страница 126: ...8 Appendix 8 3 Dimension 126 Isolated Thermocouple Input Module TC4S User s Guide R200 Honeywell September 2010 ...
Страница 127: ...8 Appendix 8 3 Dimension R200 Isolated Thermocouple Input Module TC4S User s Guide 127 September 2010 Honeywell ...
Страница 128: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...