5
. Internal Memory
5.2. I/O area of TC module conversion data
72
Isolated Thermocouple Input Module TC4S User's Guide
R200
Honeywell
September 2010
Address
Description
%UWa.b17
CH2 Temp. Max Value
%UWa.b18
CH3 Temp. Min Value
%UWa.b19
CH3 Temp. Max Value
ATTENTION
The area is cleared if a channel stops (output 0 if stoppage).
Data upload time
1.
It is the area to display update interval (time; data 1 count of an area means 0.1ms)
when updating module data for data sharing with MasterLogic 200 PLC.
2.
In case module data is not entered at a specified interval (number of operation
channel
∗
40ms) due to occupation time of PLC scan program, the real update
interval can be detected using the data of the area.
3.
In case processing data at regular intervals or using PV for control, it can be used
for setting control interval.
REFERENCE - INTERNAL
For the examples, refer to Programming.
Address
Description
%Uda.b10
CH0 Data Upload Time
%Uda.b10
CH0 Data Upload Time
%Uda.b10
CH0 Data Upload Time
%Uda.b10
CH0 Data Upload Time
Содержание TC4S
Страница 114: ...7 Troubleshooting 7 4 Error code 114 Isolated Thermocouple Input Module TC4S User s Guide R200 Honeywell September 2010 ...
Страница 126: ...8 Appendix 8 3 Dimension 126 Isolated Thermocouple Input Module TC4S User s Guide R200 Honeywell September 2010 ...
Страница 127: ...8 Appendix 8 3 Dimension R200 Isolated Thermocouple Input Module TC4S User s Guide 127 September 2010 Honeywell ...
Страница 128: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...