Page 78
STT700 Series HART/DE Option User’s Manual
Revision 1
c.
While observing the PV value at the physical process element, adjust the process
variable to the desired maximum level, and then select
Set URV.
d.
If the displayed value is satisfactory, select
Yes
to copy the Input Value to the URV in
the transmitter. If not, select
NO
and repeat this step.
4.
Verify the LRV and URV settings as follows:
a.
Call up the DE CONFIGURE display, and observe that the settings are established in
Steps 4 and 5.
b.
This concludes the procedure to manually set the operating range.