Page 70
STT700 Series HART/DE Option User’s Manual
Revision 1
Figure 11
– Input Calibration Connections
6.8 Input Calibration Procedure
6.8.1 Correct Input at the Lower Range Value (LRV)
This section describes the action to correct the input at the Lower Range Value (LRV). To begin,
enter the appropriate values before doing the calibration. Configure sensor type to mV or TC or RTD
or Ohms for the input which you are going to perform calibration. Below snapshots are examples of
sensor type TC-E.
These values are entered in Device Setup/Sensors/Sensor 1/Sensor 1 Config Params menus, thus the
first set is for LRV1 Correct and URV1 Correct and the second set is for LRV2 Correct and URV2
Correct.
1.
Select the
Correct LRV
button on the CALIBRATION display.
2.
Select the
Correct LRV
button. This message appears: