Page 46
STT700 Series HART/DE Option User’s Manual
Revision 1
Online Menu Flow
Parameter menu/
name
Description/Valid values
Advanced Configuration/Calibration
Online/Device
Setup/Advanced
Configuration/Calibration
PV Levels
Displays a graphic representation of all PV
ranges and limits for the STT700 temperature
transmitter
Calibration
Methods
The following calibration methods are available:
Apply Values: performs a Set LRV and/or Set URV
to configure the LRV/URV to applied inputs.
D/A Trim: performs an analog output calibration at
4.0000 and 20.000 mA (0% and 100% output).
Sensor 1
Calibration
S1 Cal Hi Correct
:
Perform an input 1 calibration correction by
applying process input at the configured High
calibration point.
S1 Cal Lo Correct:
Perform an input 1 calibration correction by
applying process input at the configured Low
calibration point.
S1 Reset Corrects:
Clear all user calibration adjustments.
S1 Cal Hi Records:
Displays the time and date history records for the
last three URV Correct calibrations.
S1 Cal Lo Records:
Displays the time and date history records for the
last three LRV Correct calibrations.
S1 Reset Correct Records:
Displays the time and date history records for the
last three times Reset Corrects was issued.
Sensor 2
Calibration
S2 Cal Hi Correct
:
Perform an input 2 calibration correction by
applying process input at the configured High
calibration point.
S2 Cal Lo Correct:
Perform an input 2 calibration correction by
applying process input at the configured Low
calibration point.
S2 Reset Corrects: