Revision 1
STT700 Series HART/DE Option User’s Manual
Page 19
4.3 DE Transmitter Online Configuration
Online configuration consists of establishing communication between the MC Toolkit and a
transmitter configured for DE communication. Each transmitter has a configured database, whether
new from the factory, a spare, or one to be reconfigured. In any case, the
MC Toolkit
application is
used to upload the existing configuration from the transmitter for review and editing.
4.3.1 Uploading a Transmitter Configuration
1.
Connect a DE transmitter to the MC Toolkit. Be sure that both devices have power applied.
2.
Start the
MC Toolkit
application by selecting Start / MC Toolkit on the MC Toolkit /
MCT404/202. The MC TOOLKIT Home page will be displayed, see below figure.
3.
Select the
Online
button, and establish communication between the Toolkit and the
transmitter.
4.
When the warning message for connecting to a DE device appears, select
OK
.
5.
Process and respond to the three warning pop-ups as appropriate, and then select
OK
in the
Put loop in Manual…
pop-up. The QUICK MONITOR box will be displayed. Typical Quick
Monitor dialog is shown below (note that Type will be shown as STT3000).