Page 40
STT700 Series HART/DE Option User’s Manual
Revision 1
5.2.9 Device Configuration and Parameter Descriptions
Table 9 lists descriptions of all parameters for a HART Transmitter with the Online tab menu path.
The same parameters may be accessed from the My Device tab.
Table 9
– HART Transmitter Parameters
Device Setup
Menus include:
Basic Configuration
General, Process Variables (PV), 4-20mA Outputs, Summary
Advanced Configuration
Sensors, Calibration, CVD, CVD1, CVD2, Alarm, Services,
Summary
Monitor
Dashboard, Device Status, Device Information, Diagnostics,
MSG Details
Review
Displays all parameters
Online Menu Flow
Parameter menu/
name
Description/Valid values
Online
Honeywell Logo
Photograph of a STT700 temperature
transmitter
along with the official “Honeywell”
logo
Table 10
– Basic Configuration
Online Menu Flow
Parameter menu/
name
Description/Valid values
Basic Configuration /General
Device Setup / Basic
Configuration / General
Transmitter Install
Date
Enter the date of site installation. This is a
one-time only configuration.
Tag
Enter tag identification up to eight
alphanumeric characters.
Long Tag
Enter a long tag name up to 32 alphanumeric
characters.
Date
Enter a date for user information only.
Descriptor
Enter a descriptor for user information only
(up to 16 alphanumeric characters)
Message
Enter a message up to 32 alphanumeric
characters) that will be sent to the
Display. The message will be shown on the
Display interspersed with the configured
screens. To stop displaying the message,
select “Clear Display” in the Device
Information menu.
Clear Message
Selecting this option clears the “Message”
and it will no longer be sent to the Display.
Final Asmbly num
Enter
the final assembly number of the
STT700 temperature transmitter
Basic Configuration / Process Variables