Page 64
ST 700 Series HART/DE Option User’s Manual
Revision 4.0
1.
Start the MC Toolkit application such that the
DE MAIN MENU
is displayed.
2.
Click the
Calibration
button to display the
CALIBRATION
menu.
3.
Click
Trim DAC Curr.
To display the
TRIM DAC CURRENT
box.
4.
The following outlines how to trim the output current:
a.
Click
Set Output To 0%
or
100%
. You will be prompted to confirm that you want to
place the Transmitter in output mode.
b.
Verify that the loop is in manual control. In output mode, output current is fixed at the
0% or 100% level as selected in the TRIM DAC CURRENT box in the previous step.
c.
Click
Yes
, and observe the loop current level. A meter reading of 4mA corresponds to
1 volt.
d.
Use the Toolkit to adjust the loop current to the Zero Percent level (4mA). If the
current is low, tap the
Increment
button; if the current is high, tap the
Decrement
button. Note that the value on the meter changes accordingly. If the error is large,
accelerate the adjustment rate by changing the Step Size to 10 or 100.
e.
After establishing the zero current level (4mA), click
Set Output To 100%
. A meter
reading of 20mA corresponds to 5 volts.
f.
Use the
Increment
or
Decrement
button, as necessary to adjust the output current to
20mA. When the current reaches the 20mA level, click
Clear Output
; the button will
change to half-intensity.
Содержание SmartLine ST700
Страница 88: ...Page 74 ST 700 Series HART DE Option User s Manual Revision 4 0 This page has been intentionally left blank ...
Страница 98: ...Page 84 ST 700 Series HART DE Option User s Manual Revision 4 0 This page intentionally left blank ...
Страница 115: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 101 11 9 Trend Charts ...
Страница 175: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 161 This page intentionally left blank ...
Страница 188: ...Page 174 ST 700 Series HART DE Option User s Manual Revision 4 0 20 9 Trend Charts ...