Page 138
ST 700 Series HART/DE Option User’s Manual
Revision 4.0
Online/Device
Setup/Detailed Setup
Namur Option
Click from the following:
Namur Selection:
Click to enable or
disable the Namur option for the output.
(Refer to the PV Ranges/Limits chart) for
effect on output signal.
Namur Level:
Displays a diagram of the
operating range and failsafe range of the
Analog output for Normal and Namur
configurations.
Sensors
Displays range information for the Sensor.
The following limits are read only:
LRL:
Lower range limit
URL:
Upper range limit
LTL:
Lower transducer limit
UTL:
Upper Transducer limit
Displays the following process variable values:
PV:
The current value of the PV (primary
variable: pressure input)in user selected
engineering units
SV:
The current value of the SV (secondary
variable: meter body temperature)in user
selected engineering units
Allows configuration of the process variable units.
See
Device Information
menu for details.
PV Units:
Click one of the pre-programmed
engineering units for the primary variable
(pressure input).
SV Units:
Click one of the pre-programmed
engineering units for the secondary variable
(meter body temperature).
Signal Condition
The following signal control parameters may be
configured in this menu:
PV Damping:
Enter a value for damping of
the device output. Entries may be any
floating point value from 0.00 to 32.00
seconds.
PV URV:
Upper Range Value or span (input
which represents 100% output). Range of
entries is from LTL to UTL.
PV LRV:
Lower Range Value or zero (input
which represents 0% output). Range of
entries is from LTL to UTL.
PV Xfer fnctn:
Pressure Transfer function:
Click pressure transfer function for
calculated output:
Linear
(output scaled linearly per
configured range)
Square Root
(output scaled as square root
conversion per configured range - for flow
measurements)
PV % range:
Displays the current value of
AO (analog output) in %
Содержание SmartLine ST700
Страница 88: ...Page 74 ST 700 Series HART DE Option User s Manual Revision 4 0 This page has been intentionally left blank ...
Страница 98: ...Page 84 ST 700 Series HART DE Option User s Manual Revision 4 0 This page intentionally left blank ...
Страница 115: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 101 11 9 Trend Charts ...
Страница 175: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 161 This page intentionally left blank ...
Страница 188: ...Page 174 ST 700 Series HART DE Option User s Manual Revision 4 0 20 9 Trend Charts ...