Page 88
ST 700 Series HART/DE Option User’s Manual
Revision 4.0
Non critical status
(Warning)
(continued)
in output mode during a CORRECT
procedure.
Resolution:
Check input pressure and be sure that it
matches calibrated range values (LRV and
URV). Check Meter Body. Perform an LRV or
ZERO CORRECT procedure followed by a
URV CORRECT procedure.
Electronic Module Comm
Failure
Possible causes:
There was a failure in the Electronics Module
communication section.
Resolution:
Verify the environment temperature is within
specifications. Reset the device.
If the problem persists, replace the
Electronics Module.
Display Failure
Possible causes:
The Display has been disconnected or
configuration data has been corrupted.
Resolution:
Secure Display connections and recheck. If
problem persists, reset the device. If the
problem still persists, replace the Display
Low Supply Voltage
Possible causes:
The supply voltage to the transmitter
terminals is too low or the supply voltage to
the Sensor board is too low.
Resolution:
Check that the power supply and loop
resistance are within specification. If
possible, try to increase the voltage level of
the supply. If supply voltage and loop
resistance are adequate and the problem
persists, replace the Electronics Module. If
the problem still persists, replace the Meter
Body.
No DAC Calibration
Possible causes:
No DAC calibration has been performed on
the device.
Resolution:
Perform DAC calibration for precise analog
output measurement.
Tamper Alarm
Possible causes:
Device is in Write Protect Mode and Tamper
Mode is enabled, or Tamper Alarm alone is
enabled, and outside attempts to change
device configuration exceeded the set
Tamper limit
Resolution:
Identify source of tampering. If configuration
changes are required, contact a qualified
Содержание SmartLine ST700
Страница 88: ...Page 74 ST 700 Series HART DE Option User s Manual Revision 4 0 This page has been intentionally left blank ...
Страница 98: ...Page 84 ST 700 Series HART DE Option User s Manual Revision 4 0 This page intentionally left blank ...
Страница 115: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 101 11 9 Trend Charts ...
Страница 175: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 161 This page intentionally left blank ...
Страница 188: ...Page 174 ST 700 Series HART DE Option User s Manual Revision 4 0 20 9 Trend Charts ...