Revision 4.0
ST 700 Series HA
RT/DE Option User’s Manual
Page 149
17.3 Calibrating Range
The ST 700 Basic SmartLine Pressure Transmitter supports two-point calibration. This means that
when two points in a range are calibrated, all points in that range adjust to the calibration.
The procedures in this section are used to calibrate a differential pressure (DP) Transmitter to a range
of 0 to 200 inH
2
O for example purposes. This procedure assumes that the Transmitter has been
removed from the process and is located in a controlled environment.
IMPORTANT! You must have a precision pressure source with an accuracy of 0.02% or
better to do a range calibration. Note that the factory calibrates SmartLine Pressure
Transmitter ST 700 Basic using inches of water pressure reference to a temperature of
39.2
o
F (4
o
C).
17.3.1 Correcting the Lower Range Value (LRV)
1.
Connect a power supply and the MC Toolkit to the signal terminals of the Transmitter’s
terminal block.
2.
Connect the precision pressure source to the high pressure side of the DP-type Transmitter.
3.
Turn on the power supply, and allow the Transmitter to become stable.
4.
Turn the MC Toolkit on, start the FDC application.
5.
On the
FDC
homepage, click
Online
, and establish communication with the Transmitter.
6.
Click the
My Device
menu, and choose from the following options:
a.
Device Setup \ Calibration \ Calibration Methods \ LRV Correct
7.
You will be prompted to remove the loop from automatic control. After removing the loop
from automatic control, click
OK
.
8.
When prompted, adjust the pressure source to apply pressure equal to the LRV (0%), and
press OK.
9.
When the pressure stabilizes, click
OK
.
10.
When prompted, remove pressure.
11.
On the next prompt:
Please enter current Calibration Time in 24 Hr Clock format (Hour
field)
, enter the hour portion of the calibration time in the 24Hr format HH, for example “12,”
and press
Enter
.
12.
On the next prompt:
Please enter current Calibration Time (Minute field)
, enter the
Minutes field MM (example 23), and press
Enter
.
13.
When prompted to return the loop to automatic control, press
Enter
.
17.3.2 Correcting the Upper Range Value (URV)
1.
Connect the power supply and communicator to the signal terminals of the Transmitter
terminal block.
2.
Connect the precision pressure source to the high pressure side of the DP-type Transmitter.
3.
Turn on the power supply, and allow the Transmitter to become stable.
4.
Turn on the MC Toolkit, and start the FDC application into operation.
5.
On the
FDC Homepage
, click
Online
, and establish communication with the Transmitter.
6.
Click the
My Device
menu, and select one of the following options:
a.
Device Setup \ Calibration \ Calibration Methods \ URV Correct
7.
You will be prompted to remove the loop from automatic control. Click
OK
.
8.
When prompted, adjust the pressure source to apply pressure equal to the URV (100%), and
click
OK
.
9.
When pressure stabilizes, click
OK
.
Содержание SmartLine ST700
Страница 88: ...Page 74 ST 700 Series HART DE Option User s Manual Revision 4 0 This page has been intentionally left blank ...
Страница 98: ...Page 84 ST 700 Series HART DE Option User s Manual Revision 4 0 This page intentionally left blank ...
Страница 115: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 101 11 9 Trend Charts ...
Страница 175: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 161 This page intentionally left blank ...
Страница 188: ...Page 174 ST 700 Series HART DE Option User s Manual Revision 4 0 20 9 Trend Charts ...