Revision 4.0
ST 700 Series HA
RT/DE Option User’s Manual
Page 39
PV Damping
Enter a value for damping of the device output.
Entries may be any value from 0.00 to 32.00
seconds.
SV Units
Click the relevant unit for measurement of the
Secondary Variable (Meter Body Temperature).
The available measurements are:
o
C ,
o
F,
o
R, Kelvin
Write Protect
Displays the current configuration of the write
protect function. Write Protect is “Enabled” if either
the write protect jumper on the electronics board is
in the
ON
position or the firmware write protect has
been enabled.
Online/Device
Setup/Calibration
PV Levels
Displays a graphic representation of all PV ranges
and limits for the ST 700 Pressure Transmitter
Calibration Methods
The following calibration methods are available:
Apply Values:
Performs a Set LRV and/or
Set URV to configure the LRV/URV to
applied inputs.
Enter Values:
Enter desired LRV and URV
value to configure the desired operating
range. Valid entries are from LTL to UTL
(lower/upper transducer limits).
D/A Trim:
Perform an analog output
calibration at 4.00 and 20.00mA (0% and
100% output).
Zero Trim:
Perform an input calibration
correction by applying process input at zero.
LRV Correct:
Perform an input calibration
correction by applying process input at the
configured LRV level.
URV Correct:
Perform an input calibration
correction by applying process input at the
configured URV level.
Reset Corrects:
Clear all user calibration
adjustments.
Filter Performance
Selection
Configure the desired performance for the Output
Speed of Response Filter. Select from:
Standard SOR :
Excellent speed of
response to input changes with optimal noise
performance
Fast SOR:
Fastest speed of response to
input changes
Correct URV
Records
Displays the time and date history records for the last
three URV Correct calibrations.
Correct LRV
Records
Displays the time and date history records for the last
three LRV Correct calibrations.
Zero Trim Records
Displays the time and date history records for the last
three Zero Trim calibrations.
Reset Correct
Records
Displays the time and date history records for the last
three times Reset Corrects was issued.
Содержание SmartLine ST700
Страница 88: ...Page 74 ST 700 Series HART DE Option User s Manual Revision 4 0 This page has been intentionally left blank ...
Страница 98: ...Page 84 ST 700 Series HART DE Option User s Manual Revision 4 0 This page intentionally left blank ...
Страница 115: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 101 11 9 Trend Charts ...
Страница 175: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 161 This page intentionally left blank ...
Страница 188: ...Page 174 ST 700 Series HART DE Option User s Manual Revision 4 0 20 9 Trend Charts ...