Page 140
ST 700 Series HART/DE Option User’s Manual
Revision 4.0
The following sections offer some examples as to how to edit the configuration parameters and
execute Methods.
16.2.10
Procedure to Enter the Transmitter Tag
1.
From the
My Device
menu, make the following menu selections:
Shortcuts > Device Setup > Basic Setup > Device Information > Tag
.
2.
Click
Edit
. The
Tag
screen will be displayed.
3.
Key in the tag name (for example: ST 700) which can be a maximum of eight characters.
4.
Click
OK
. The
Send to Device
screen will be displayed.
5.
Click the
Tag
check box.
6.
Click
Send
to download the change to the Transmitter, or Click
Return
to continue making
changes.
16.2.11
Selecting the Process Variable (PV) Unit of Pressure
Measurement
Engineering units affect the values of the LRV and URV. After changing the PV
engineering units to the Transmitter, verify changes to the units paramter, the LRV, and the
URV.
The pressure measurement can be displayed in one of the pre-programmed engineering units.
1.
From
My Device
menu, navigate to:
Shortcuts > Device Setup > Basic Setup > PV Units
2.
Click
Edit.
You will be warned that if you change the value of the variable it will change the
loop current, which may upset the control process.
3.
Click
Yes
to continue. The PV Unit screen will be displayed with a list of measurement units,
as follows
:
inH
2
O
psi
Pa
inH
2
O@4
o
C
inHg
bar
kPa
mmH
2
O@4
o
C
ftH
2
O
mbar
Torr
cmH
2
O@4
o
C
mmH
2
O
g/cm
2
Atm
mH
2
O@4
o
C
mmHg
kg/cm
2
MPa
4.
Click the desired
PV Unit
, and click
OK
. A Post Edit action message will be displayed,
indicating if you click this value, the variables that use it as the units code will start in the
previous units until this value is sent to the Transmitter.
5.
Click
OK
to continue or
Abort
to discard the change.
6.
Click
Send
. The Send to Device screen will be displayed.
7.
Click the
PV Unit
check box.
8.
Click
Send
to download the change to the Transmitter or
Return
to continue making
changes.
Содержание SmartLine ST700
Страница 88: ...Page 74 ST 700 Series HART DE Option User s Manual Revision 4 0 This page has been intentionally left blank ...
Страница 98: ...Page 84 ST 700 Series HART DE Option User s Manual Revision 4 0 This page intentionally left blank ...
Страница 115: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 101 11 9 Trend Charts ...
Страница 175: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 161 This page intentionally left blank ...
Страница 188: ...Page 174 ST 700 Series HART DE Option User s Manual Revision 4 0 20 9 Trend Charts ...