Certification
Explosion-Proof Specification
• ATEX (DEMKO 17 ATEX 1872X)
II 2 GD
Ex db IIC T6 Gb
Ex tb IIIC T85°C Db
Tamb −40 to +65°C
1) Manufacturer information
2) Electrical rating
3) ATEX and IECEx protection marking
4) Chinese EPUP marking
5) Revision check box
6) QAN notified body number
7) WEEE marking
8) Country of origin
9) Serial number and part number
• IECEx (IECEx UL 17.0038X)
Ex db IIC T6 Gb
Ex tb IIIC T85°C Db
Tamb −40 to 65°C
• cULus
Class I, Division 1 & 2, Groups B, C and D
Class II, Division 1 & 2, Groups E, F and G
Class I, Zone 1, AEx db IIC T6
Zone 21, AEx tb IIIC T85°C, IP6X
Ex db IIC T6 GbX
Ex tb IIIC T85°C DbX
Tamb −40 to +65°C, Temp Code T6
Specific conditions of use:
1. Do not repair flameproof joints.
2. See intallation manual for guidance for the user to minimize the risk
from electrostatic discharge.
3. All accessories are NOT part of the explosion-proof certificate.
54