Installation
2.7
Securing the Detector to a Wall
The Sensepoint XRL transmitter has an integral mounting plate
consisting of four mounting holes on the transmitter body. The
transmitter may be fixed directly to a surface mounting, or to a
horizontal or vertical pipe/structure, 40.0 to 70.0 mm (1.6 to 2.8 inches)
in diameter/cross section. The pipe mounting bracket accessory
(optional) may be used for this purpose.
CAUTION
Before starting installation, make sure that the system controller or
external power source is switched off.
,1&
20
&2
1. Determine where the detector is to be
placed. Mark and drill holes as
required.
2. Secure the detector in its mounting
position with suitable fixings
appropriate to the mounting surface.
Do not over-tighten.
2.8 Cable Connections
The cable used must be appropriate for the hazardous area
classification and meet local, national and/or company regulations.
The use of industrial grade, screened field cable is recommended. Make
sure that cable has a suitable insulation as cable can be connected to
metal parts of Sensepoint XRL enclosure inside.
22