How to enable/disable an IO line
How to enable/disable an IO line
NA
These operations are not applicable for a Network Node.
An interface input/output line can be disabled or enabled. You will need to
know the IO line, device and loop numbers, these numbers can be found
in the site speci
fi
c documents held by the person responsible for the
fi
re
system.
An output line of an interface unit may be assigned
to a sector and can only be disabled by disabling that
sector. This has the effect of also disabling all other
devices in the sector.
a. Press the
MENU ON/OFF
key.
b. Press the F1 button to select
[Control]
.
c. Press the F4 button to select
[UserCode]
. At the
fl
ashing cursor using
the keypad input your PIN code and then press the
Enter
button.
d. To disable an IO line press the F2 button to select
[Disable]
or press
the F1 button to select
[Enable]
, the display reads ‘Enable’ or ‘Disable’.
e. Press the F2 button to select
[IO Line]
. At the
fl
ashing cursor using the
keypad input an IO line number.
f. Press the F2 button to select
[Device]
. At the
fl
ashing cursor using the
keypad input a device number from a range 1 to 200.
g. Press the F2 button to select
[Loop]
. At the
fl
ashing cursor using the
keypad input a loop number from a range 1 to 2.
h. Press the F2 button to select
[Enter]
. Notice the action has been
processed and a message appears on the display: ‘IO line disabled/
enabled at Card n’. The disablement light will illuminate upon
disablement of an IO line.
How to enable/disable auxiliary relay
The control panel / network node has two
auxiliary relays that provides voltage free contacts
to control external equipment in the event of a
fi
re
or fault condition. The operation of the relays can
be disabled or enabled.
a. Press the
MENU ON/OFF
key.
b. Press the F1 button to select
[Control]
.
c. Press the F4 button to select
[UserCode]
.
At the
fl
ashing cursor using the keypad input
your PIN code and then press the
Enter
button.
d. To disable the auxiliary relay press the F2
button to select
[Disable]
or press the F1
button to select
[Enable]
. This puts ‘Disable’
or ‘Enable’ on the display.
e. Press the F4 button three times selecting
<etc>
on each occasion and then press the
F2 button to select
[Aux Rly]
. At the
fl
ashing
cursor using the keypad input an auxiliary
relay number or range (1-2).
f. Press the F2 button to select
[Enter]
.
Notice the action has been processed and a
message appears on the display: ‘Aux Rly n
disabled/enabled’. The Disablement light will
illuminate upon disablement of an auxiliary
relay.