Vigilon fire alarm system

Typical fault messages

The table below shows some of the more typical fault messages and indications that may appear at the panel if there are faults in 
the system. It also gives the meaning and possible recti

fi

 cation action for each fault.

On

Flashing

Message

Indication

Meaning

Action

FARE Faulty

Fault

   

Fault/Dis

The Fire Alarm Routing Equipment FARE is 
faulty.

Check short circuit or signal transmission 
failure at FARE

Mains failed

Fault

  

Power Fault

The mains supply to the control panel has failed.

Restore the mains supply to the control 
panel.

Battery 
discharged n

Fault

  

Power Fault

The battery supply to the Control Panel is fully 
discharged.

Check the battery and replace if 
necessary.

Battery 
disconnected

Fault

  

Power Fault

The battery supply to the Control Panel has been 
disconnected.

Reconnect the battery.

Monitored line 
input OC or SC

Fault

The monitored line input has an open or short 
circuit fault.

Check the wiring and ensure the end-of-
line device is connected in the circuit.

Master Alarm(s) 
OC or SC n

Fault

  

Sounder

There is an open or short circuit fault on the 
master alarm wiring.

Check the wiring. Ensure the end-of-line 
device is connected in the circuit.

Lost Device

Fault

  

Sounder

The Device is not communicating with the 
Control Panel via the Loop. Additional indication 
given if it is a Sounder device.

Check the connections to the device.

Wiring changed 
SC at card n

Fault

There is a short circuit on the loop n wiring.

Identify the device where a cable fault 
has occurred and remove the fault.

Interface input 
OC /SC

Fault

There is an open or short circuit on the input line 
of an interface.

Locate and remove the wiring fault. 
Ensure the end-of-line device is 
connected in the circuit.

Device Mains 
failed

Fault

There is a mains supply failure at an interface 
unit, repeat panel or mimic panel

Check the fuse and mains supply to the 
equipment.

Device Battery 
fault

Fault

The battery supply at an interface unit, repeat 
panel or mimic panel has failed the load test.

Check the battery and replace if 
necessary.

Содержание GENT

Страница 1: ... Network node Fire detection and alarm system Vigilon Fire System GENT 2015 Designed to EN54 Pt 2 4 Healthy 15 45 Fault System Fault Test Fire Power Power Fault Fault Dis Disablement Sounder Previous Next Delay Verify Active Fire Routing O P ...

Страница 2: ...o set the system clock 24 How to use the integral printer 25 To Switch On Off the Printer 25 To action a Paper Feed 25 To conduct a Printer Test 25 How to enable disable Sensing 25 How to enable disable a zone 26 How to manually switch On Off FARE 26 How to manually Disable Enable FARE 27 How to manually Disable Enable FPE 27 How to enable disable an IO line 28 How to enable disable auxiliary rela...

Страница 3: ...y hidden in the main text This is either a caution to prevent damage to the equipment or a warning to inform of dangerous conditions that may result in injury or death Symbol Keys What you will see What you will hear A fire condition LED illuminated On LED illuminated Flashing NA Not applicable Abbreviations FARE Fire Alarm Routing Equipment FPE Fire Protection Equipment LED Light emitting diode l...

Страница 4: ...nspected daily to ensure That a normal indication is given at the control and indicating equipment That any previously indicated fault conditions have received appropriate attention All system events are entered into the Log Book for future reference That the use of the area s that are inspected has not changed since the system was designed That no unsafe practices that could lead to fire are bein...

Страница 5: ...rence of a fire fault or disablement event in the protect premises the event is quickly indicated at a control and indicating equipment The control and indicating equipments are installed in accessible location and can be operated by the person responsible for the fire system Control panel The control panel is the heart of the system It is normally located near to the main entry or exit point of t...

Страница 6: ... the protected premises Repeat panel provides system indications and controls Repeat indicator panel provides system indications Vigilon Fire System GENT 2015 Panel healthy 15 45 Active Fault Dis Fire Routing O P Zonal Mimic panels There may also be a number of mimic and zonal mimic panels installed in the protected premises to provide visual indications in a graphical and zonal format Normally on...

Страница 7: ... 26 27 28 29 30 30 32 Zones Active Fault Dis Fire Routing O P Fault System Fault Test Fire Power Power Fault Disablement Sounder 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32 Zones Previous Next Delay Verify 4 2 3 5 6 7 8 9 0 U1 U3 U4 Fire Z X C V B N M Sound Alarms Silence Alarms Reset Cancel Buzzer Menu On Off F4 F3 F1 F2 1 Insert Q W E R T Y U I O P U2 D...

Страница 8: ...n the fire detection and alarm system System Fault amber When illuminated it indicates that a fault has occurred with the system processor It is important to investigate this fault because the fire system may not be able to detect fires Disablement amber When illuminated it indicates that a part of the system has been disabled Active red When illuminated it indicates the Output to the Fire Alarm R...

Страница 9: ...sponds to one of the function buttons and pressing a button will select the option which appears above it on the display Cancel buzzer The Cancel Buzzer button when pressed will stop the internal panel buzzer from sounding Sound alarms Pressing the Sound Alarms button will sound all the system alarms This button is only pressed in an emergency or at other agreed times for example when conducting a...

Страница 10: ...onfigured during commissioning to action user defined tasks such as the disablement of devices in areas where smoke may be generated due to maintenance work or where plant shutdown is required Fire The two fire events scroll buttons on the keyboard operate in exactly the same way as the two first level access fire scroll buttons on the front door These buttons are active when the door is open Qwer...

Страница 11: ...24 25 26 27 28 29 30 30 32 Zones Fault System Fault Delay Test Fire Power Power Fault Verify Disablement Sounder Active Fault Dis Fire Routing O P The FIRE events when displayed can be scrolled through by utilising the first level controls located as shown on the panel front door How to operate a U button The U1 to U4 buttons may have been configured during commissioning to action user defined tas...

Страница 12: ...dicates there is active Fire routing output to Alarm Receiving Centre Who would know this is a test as they would have been advised before the weekly test At this point the test key is retained in the call point Check the alarms are sounding in the building and an indication is given of the fire event Turn the test key anticlockwise one quarter of a turn and remove it from the call point With the ...

Страница 13: ...re Routing O P If configured this light indicates there is an active Fire routing output to Alarm Receiving Centre to initiate Fire fighting action With the panel door open To cancel buzzer You can stop the panel buzzer from sounding Press Cancel buzzer Display reads Buzzer cancelled To silence alarms When the emergency is over the alarm sounders can be silenced Press Silence alarms Display reads ...

Страница 14: ...Flashing Active Fault Dis Fire Routing O P If configured this light indicates there is an active Fire routing output to Alarm Receiving Centre to initiate Fire fighting action With the panel door open To cancel buzzer You can stop the panel buzzer from sounding Press Cancel buzzer Display reads Buzzer cancelled To silence alarms When the emergency is over the alarm sounders can be silenced Press S...

Страница 15: ...ay be indicated by a flashing zone number all other zones in fire give a steady indication NA The zone indicators are not applicable for Network Node Each fire is logged in the Historic Events log which can be recalled using the menus See How to view the Historic Events To verify an alarm If required by site procedures Upon receipt of a fire condition the alarm sounders in the system can be delaye...

Страница 16: ...le for the fire alarm system must attempt any fault rectification work For advice please call your servicing organisation see contact details in the Log book With the panel door open To cancel buzzer You can stop the panel buzzer from sounding Press Cancel buzzer Display reads Buzzer cancelled What must be done You need to ensure the panel is returned to normal condition All fault repairs must be ...

Страница 17: ...t circuit fault Check the wiring and ensure the end of line device is connected in the circuit Master Alarm s OC or SC n Fault Sounder There is an open or short circuit fault on the master alarm wiring Check the wiring Ensure the end of line device is connected in the circuit Lost Device Fault Sounder The Device is not communicating with the Control Panel via the Loop Additional indication given i...

Страница 18: ...er alarms in the system are disabled Previous Next Fault System Fault Delay Test Fire Power Power Fault Verify Disablement Sounder 15 45 Disable 1 Time 15 43 44 Mon 16 March 2015 Device Disabled at card 1 Active Fault Dis Fire Routing O P What must be done Investigate the reason for the disablement and re instate the devices if appropriate Record the event Where necessary make an entry in the log ...

Страница 19: ...ication is given if it is a sounder device If manually disabled then investigate and if appropriate re enable the device Sector disabled at card n Disablement Sounder The fire alarm sector on loop n has been manually or automatically disabled If manually disabled then investigate and if appropriate re enable the sector Disabled Aux Relay n Disablement The auxiliary relay n in the control panel has...

Страница 20: ...on mode If the time taken between key presses exceeds five minutes then the control panel will automatically remove the menu options from the display and give a system status indications The Params option is a Help function to provide information to the user regarding the type of input data required Most of the functions in the Control Setup and TestEng menu options are protected with password ent...

Страница 21: ...ng of the fire alarm system The customer PIN code is set up for the end user The person responsible for the fire alarm system should be aware of this PIN code For security the PIN should be changed on a regular basis A previously created PIN can be changed a Press the MENU ON OFF button b Press the F4 button to select Test Eng c Press the F4 button to select UserCode Use the keypad to input your e...

Страница 22: ...ew events at another node in a networked system then you will need the node number Select Node and enter the node number The event number 1 is always the most recent event f Press the F2 button to select Enter Notice the required event s are displayed or printed depending on your selection Cards inside the control panel The control panel uses the following card reference numbers Card 0 is always t...

Страница 23: ...s still present and has not cleared You can view all active Fire Fault or Disablement events a Press MENU ON OFF b Press the F3 button to select Info Ignore step c if an external printer is not fitted or is switched off c To display the event s Press the F1 button to select Display Notice Display appears on the display To print the event s Press the F2 button to select Print Notice Print appears o...

Страница 24: ...s are now flashing f Press the F2 or F3 key to Retard or Advance to the desired setting g Press the F1 key to select Next Check that the Date digits are now flashing h Press the F2 or F3 key to Retard or Advance to the desired setting i Press the F1 key to select Next Check that the Month digits are now flashing j Press the F2 or F3 key to Retard or Advance to the desired setting k Press the F1 ke...

Страница 25: ...These operations are not applicable for a Network Node It is only possible to disable a Manual Call Point MCP individually not as part of a range DISABLING A MCP IS NOT RECOMMENDED A sensing device such as a sensor or MCP in the system can be disabled enabled You will need the device and loop numbers this information can be found in the site specific documents held by the person responsible for th...

Страница 26: ...e keypad input a zone number or range 1 128 f Press the F2 button to select Enter Notice the action has been processed and a message appears on the display Zone n enabled or Zone n disabled The Disablement light will be illuminated upon disablement of any zone How to manually switch On Off FARE The fire alarm routing output via the FARE interface that signals the Alarm Receiving Centre can be manu...

Страница 27: ...played f Press the F1 button to select FARE g Press the F2 key to select Enter the display shows either FARE Disabled or FARE Enabled message How to manually Disable Enable FPE All the FPE interfaces in a system that signal to all fire protection equipment can be manually disabled or enabled Select from the panel menu a Press the MENU ON OFF key b Press the F1 button to select Control c Press the ...

Страница 28: ...lect Loop At the flashing cursor using the keypad input a loop number from a range 1 to 2 h Press the F2 button to select Enter Notice the action has been processed and a message appears on the display IO line disabled enabled at Card n The disablement light will illuminate upon disablement of an IO line How to enable disable auxiliary relay The control panel network node has two auxiliary relays ...

Страница 29: ...sible for the fire alarm system a Press the MENU ON OFF button b Press the F3 button to select Info Ignore step c if an external printer is not fitted or is switched off c To display a device label press the F1 button to select Display or to print a device label press the F2 button to select Print Notice Display or Print appears on the screen d Press the F4 button to select etc e Press the F2 butt...

Страница 30: ... An interface unit can have up to four input output IO lines Each line may have been given a label for display during an event To view an IO line label you will need to know the interface device address the IO line number and the loop number which can found in the site specific documentation held by the person responsible for the fire alarm system a Press the MENU ON OFF button b Press the F3 butt...

Страница 31: ... NA The Loop map option is not applicable for Network Node A map provides information on devices that are connected to a loop off a control panel in a fire alarm network a Press the MENU ON OFF button b Press the F3 button to select Info Ignore step c if an integral printer is not fitted or is switched off c To display a loop map press the F1 button to select Display or to print a loop map press t...

Страница 32: ... Up c Press the F4 button to select UserCode A message is displayed Enter access code followed by a flashing cursor Use the keypad to input your PIN and then press the Enter button d Press the F4 button once to select etc e Press the F1 button to select Modify Notice Modify appears on the display f Press the F1 button to select Label Notice Label appears on the display g Press the F3 button to sel...

Страница 33: ... the F4 button once to select etc e Press the F1 button to select Modify Notice Modify appears on the display f Press the F1 button to select Label Notice Label appears on the display g Press the F2 button to select IO Line Notice IO Line followed by a flashing cursor on the display Using the keypad enter an input output number from a range 1 to 4 h Press the F3 button to select Device Notice Devi...

Страница 34: ...us label appears on the display with a flashing first character to prompt you to edit the label If there is no label then the line is blank j Using the keypad to enter a label of up to 32 characters in length and then press the Enter button How to edit a local panel label A label is normally given to the control panel to identify its location in a network A previously entered label can be modified...

Страница 35: ...UserCode Notice a message on the display Enter access code followed by a flashing cursor Use the keypad to input the PIN and then press Enter button d Press the F4 button once to select etc e Press the F1 button to select Modify Notice Modify appears on the display f Press the F1 button to select Label Notice Label appears on the display g Press the F4 button once to select etc h Press the F3 butt...

Страница 36: ...nto the yellow arm d Hook the front cover onto the top edge of the call point assembly and then push the bottom edge down until a click is heard and the cover shuts onto the main assembly Check both hooks on the top of the front cover are locked onto the call point assembly e Turn the test key anticlockwise one quarter of a turn such that the glass is held under the yellow arm The call point is no...

Страница 37: ...e allen key flat ended screw driver dependent on panel construction b Remove the old paper roll from inside of the inner door assembly Where the paper roll holder is vertically above the mechanism then do d e and then c c Fit the new paper roll to the holder d Insert paper from the new paper roll into the printer mechanism e Turn the paper feed wheel located on the outside of the inner door downwa...

Страница 38: ...stomer level 2 password however under normal circumstances it is unnecessary to use this function a Press the MENU ON OFF key b Press the F1 button to select Test Eng c Press the F4 button to select UserCode Notice a flashing cursor and a message on the display Enter access code Use the keyboard to input your password and then press the Enter button d Press the F1 button to select Loop and F1 butt...

Страница 39: ...39 Vigilon fire alarm system This page has been intentionally left blank ...

Страница 40: ...be disposed of via a suitable recycling centre and in accordance with national or local legislation Gent by Honeywell Novar Systems Limited Manufactured by Honeywell Life Safety Systems 140 Waterside Road Hamilton Industrial Park Leicester LE5 1TN United Kingdom 13 DoP Product No 026 CPR 2013 VIG1 24 026 CPR 2013 VIG1 24 NP 026 CPR 2013 VIG1 24 PO 026 CPR 2013 VIG1 24 SP 027 CPR 2013 VIG1 72 027 C...

Отзывы: