19
Vigilon fire alarm system
Typical Disablement Messages
The following table shows some typical disablement messages and indications that may appear at the panel.
On
Flashing
Message
Indication
Meaning
Action
FARE Disabled
Fault
Fault/Dis
The Fire Alarm Routing Equipment FARE has
been Disabled.
If manually disabled then investigate and
if necessary re-enable FARE.
Zone Disabled
at card n
Disablement
Fault/Dis
The zone speci
fi
ed has been manually or
automatically disabled.
If manually disabled then investigate and
if necessary re-enable the zone.
Device disabled
at card n
Disablement
Sounder
The device connected to the loop circuit has
been manually or automatically disabled.
Additional indication is given if it is a sounder
device.
If manually disabled then investigate and
if appropriate re-enable the device.
Sector disabled
at card n
Disablement
Sounder
The
fi
re alarm sector on loop n has been
manually or automatically disabled.
If manually disabled then investigate and
if appropriate, re-enable the sector.
Disabled Aux
Relay n
Disablement
The auxiliary relay n in the control panel has
been manually or automatically disabled.
If manually disabled then investigate and
if appropriate, re-enable the aux relay.
Master alarm(s)
disabled
Disablement
Sounder
The master alarms have been manually or
automatically disabled.
If manually disabled then investigate
and if appropriate, re-enable the master
alarms.
Any changes to the setting of an automatic disablement must only be attempted by a trained engineer who is
responsible for the
fi
re alarm system, see contact details in the Log book.