8
Description of controls and indications
Indicators
Description
Display
The Display provides messages of the system status / events by means of 8 lines by 40 characters per line display.
Zones 1
(red)
Secret-until-lit fire zone indicators. When the “Zones” text and number(s) are illuminated it indicates that a FIRE has
been detected in the indicated zone(s).
NA
The Zone indicators are not applicable for a Network node.
Power
(green)
When illuminated it indicates that a supply to the panel is present.
Fire
(red)
When illuminated it indicates that a FIRE has been detected in the protected premises.
Verify
(amber)
When illuminated it indicates that the Verify button has been pressed and the alarm sounders in the system are
delayed from sounding.
Fault
(amber)
When illuminated it indicates that a FAULT has been detected in the fire detection and alarm system.
System Fault
(amber)
When illuminated it indicates that a fault has occurred with the system processor. It is important to investigate this
fault because the fire system may not be able to detect fires.
Disablement
(amber)
When illuminated it indicates that a part of the system has been disabled.
Active
(red)
When illuminated it indicates the Output to the Fire Alarm Routing Equipment is active.
Fault/Dis
(amber)
When illuminated steady (always with the DISABLEMENT light) it indicates the Output to Fire Alarm
Routing Equipment is disabled.
Fault/Dis
(amber)
When illuminated flashing (always with the FAULT light) it indicates that there is a fault at the Fire Alarm
Routing Equipment.
Power Fault
(amber)
When illuminated it indicates the battery or mains supply to the panel has failed.
Sounder
(amber)
When illuminated (always with either the FAULT light or the DISABLEMENT light) it indicates that there is a sounder
fault (flashing indication) or sounder disablement (steady indication).