33
Vigilon Plus fire alarm system
How to edit an Input/output line label
NA
This operation is not applicable for a
Vigilon Plus Network Node
.
Each input / output (IO) line of an interface unit can be given a
label and a previously entered label can be modified. To edit an IO
line label you will need to know the IO line number, interface device
number and the loop number it is connected to. You can find this
information in the site specific documentation, held by the person
responsible for the fire alarm system.
a.
Press the
MENU ON/OFF
button.
b. Press the F2 button to select
[Set Up].
c. Press the F4 button to select
[UserCode]
. Notice a message on
the display ‘Enter access code’, followed by a flashing cursor. Use
the keypad to input your PIN and then press
Enter
button.
d. Press the F4 button once to select
<etc>.
e. Press the F1 button to select
[Modify]
. Notice ‘Modify’ appears on
the display.
f. Press the F1 button to select
[Label]
. Notice ‘Label’ appears on the
display.
g. Press the F2 button to select
[IO Line]
. Notice ‘IO Line’ followed by
a flashing cursor on the display. Using the keypad enter an input/
output number from a range 1 to 4.
h. Press the F3 button to select
[Device]
. Notice ‘Device’ followed by
a flashing cursor appears on the display. Use the keypad to input a
Device number from a range 1 to 200.
i. Press the F2 button to select
[Loop]
. Notice ‘Loop’ followed by
a flashing cursor on the display. Use the keypad to input a loop
number from a range 1 - 6.
j. Press the F2 button to select
[Enter]
. Notice the
previous label appears on the display with a flashing
first character to prompt you to edit a label. If there is
no label then the line is blank.
k. Using the keypad enter a label of up to 32 characters
in length and then press the
Enter
button.