15
Vigilon Plus fire alarm system
Multiple fires
Next
Previous
F2
F3
FIRE
Use the [Previous] or [Next] buttons or with the outer door open you can to scroll the fire events.
The 1st Fire will always appear at top of display. All subsequent fires appear beneath the 1st Fire.
Zones 1
The zonal indicators show zones in fire condition. If the panel is configured, the first zone to go into a fire
condition may be indicated by a flashing zone number, all other zones in fire give a steady indication.
NA
The zone indicators are not applicable for Vigilon Plus Network Node.
Each fire is logged in the Historic Events log, which can be recalled using the menus. See How to view the Historic Events.
To verify an alarm
(If required by
site procedures)
Upon receipt of a fire condition the alarm sounders in the system can be delayed from sounding by using the Verify button.
This allows time to investigate the cause of the alarm.
Note the delayed sounders will operate after the verify period has timed-out.
Press:
VERIFY
Verify