background image

HONEYWELL EMERGENCY NOTIFICATION MANAGER

 

29 

39-00008-1 

 

 

 

Output Event Suppression 

Event  suppression  results  from  automatic  panel  suppression 
as well as programming. Following is a list of factors to keep in 
mind  during  system  setup  to  achieve  the  desired  event 
suppression. 

 

General Considerations for MN and Fire: 

•  General  zones  and  logic  zones  are  not  suppressed  by  an 

MN  or  Fire  event.  Output  device  and  zone  map 
programming  determine  whether  an  output  will  be 
suppressed, not the state of the zone. 

•  A  general  zone  tracks  the  type  of  event  (i.e.  MN  or  Fire) 

that  initiates  its  activation,  and  its  outputs  will  be 
suppressed  or  resounded 

automatically 

by 

panel 

programming. Suppression of outputs activated by general 
zones  is  dependent  upon  the  event  type  that  initiated  its 
activation. 

•  Each  general  zone  must  be  dedicated  to  a  single  event 

type.  If  a  general  zone  is  used  for  MN,  that  zone  cannot 
also be used for fire, security, etc.. 

•  An output device, such as a horn or strobe, can be mapped 

to multiple zones. The zones can be general zones, special 
function  zones,  logic  zones,  or  releasing  zones.  These 
zones do not need to be the same event type: for example, 
a  general  zone  used  for  MN  and  a  general  zone  used  for 
Fire can be mapped to the same strobe. 

•  A logic zone does not automatically track the type of event 

that  initiates  its  activation.  Logic  zones  must  be  written  to 
ensure suppression. See examples below. 

MN IS THE HIGHEST PRIORITY

 

Zones: 

•  It  is  crucial  that  logic  zones  be  written  conditionally  to 

ensure  suppression.  The  following  examples  illustrate  two 
ways to achieve suppression using logic equations. 

 

Example 1

Output   suppression   using   Logic   Zone   Programming   and 
Special Function Zone ZF20 
Logic  equation  ZL1  =  AND(OR(Z10,Z11,Z12),NOT(ZF20)), 
mapped  to  an  output  that  is  used  for  fire  and  suppressed 
during MN. 
Z10, Z11, and Z12 are dedicated fire zones. ZF20 is the MN 
alarm zone. 
If  Z10,  Z11,  or  Z12  is  active,  and  ZF20  is  not,  ZL1  will  go 
active. 
If any MN alarm occurs, ZL1 will go inactive, and any outputs 
mapped to it may be suppressed. 

Example 2

Output suppression using Logic Zone Programming and MN- 
dedicated General Zones 
Logic   equation   ZL2   =   AND(OR(Z10,Z11,Z12),NOT(Z2)), 
mapped  to  an  output  that  is  used  for  fire  and  suppressed 
during MN. 
Z10,  Z11,  and  Z12  are  dedicated  fire  zones.  Z2  is  an  MN 
alarm zone. 
If Z10, Z11, or Z12 is active, and Z2 is not, ZL2 will go active. 
If  Z10,  Z11,  or  Z12,  and  Z2  are  active,  ZL2  will  go  inactive, 
and any outputs mapped to it may be suppressed. 

 

Outputs: 

•  All  outputs  used  for  MN  must  be  programmed  as  non- 

silenceable.  This  includes  those  outputs  that  are  shared 
between MN and other events, such as Fire. 

•  Dedicated Fire outputs can be programmed as silenceable 

or non-silenceable. 

•  All silenceable outputs will be suppressed at the start of an 

MN event.* 

•  All devices programmed with strobe Type IDs, as well as all 

intelligent sounder bases, will be suppressed regardless of 
silenceable programming at the start of an MN event.* 

*Zone  map  programming  will  then  be  re-evaluated, 
and  if  a  device  contains  ZF20,  or  any  general  zone 
dedicated to MN that is active, in its zone map, it will 
be re-activated. 

•  An  output  programmed  with  a  releasing  Type  ID,  or 

programmed with an active releasing zone in its zone map, 
will not be suppressed. 

 

Audio: 

•  Fire sequences playing on a DAL (digital audio loop) will be 

silenced, and the XLS-DVC will sound the MN Active Tone 
while fire is suppressed. 

•  Fire  sequences  on  an  XLS-DVC  will  not  sound,  and  the 

XLS-DVC  will  sound  the  MN  Active  Tone  while  fire  is 
suppressed. 

 

Drill and custom drill operation is blocked while fire activations 
are suppressed. This prevents activation of fire outputs while a 
Mass Notification is in progress. 

When  an  MN  alarm  is  cleared,  suppressed  outputs  will 
reactivate,  even  if  they  were  silenced  prior  to  being 
suppressed 

FIRE IS THE HIGHEST PRIORITY

 

 

Zones: 

•  It  is  crucial  that  logic  zones  be  written  conditionally  to 

ensure suppression. 

Example 1

Output  suppression  using  Logic  Zone  Programming  and 
Special Function Zone ZF20 
Logic   equation   ZL1   =   AND(ZF20,NOT(OR(Z1,Z2,Z3))), 
mapped to an output that is used for both fire and MN. 
Z1,  Z2,  and  Z3  are  dedicated  fire  zones.  ZF20  is  the  MN 
alarm zone. 
If  ZF20  is  active,  an  Z1,  Z2,  or  Z3  are  not,  ZL1  will  go 
active. 
If  Z1,  Z2,  or  Z3  subsequently  goes  active,  ZL1  will  go 
inactive, and any outputs mapped to it may be suppressed. 

 

Example 2

Output  suppression  using  Logic  Zone  Programming  and 
Fire-dedicated General Zones. 
Logic  equation  ZL2  =  AND(Z11,NOT(OR(Z1,Z2,Z3))).  Z1, 
Z2, and Z3 are dedicated fire zones. 
Z11 is an MN alarm zone. 
If  Z11  is  active,  and  Z1,  Z2,  or  Z3  are  not,  ZL2  will  go 
active. 
If Z1, Z2, or Z3 subsequently go active, ZL2 will go inactive, 
and any outputs mapped to it may be suppressed. 

Содержание EBI XLS MASS NOTIFICATION SYSTEM

Страница 1: ...rer s recommendations State and local codes and the recommendations contained in the Guide for Proper Use of System Smoke Detectors which is made available at no charge to all installing dealers This document can be found at http www systemsensor com appguides A study by the Federal Emergency Management Agency an agency of the United States government indicated that smoke detectors may not go off ...

Страница 2: ...mission systems are recommended The most common cause of life safety system malfunction is inadequate maintenance To keep the entire life safety system in excellent working order ongoing maintenance is required per the manufacturer s recommendations and UL and NFPA standards At a minimum the requirements of NFPA 72 shall be followed Environments with large amounts of dust dirt or high air velocity...

Страница 3: ...damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal removal This system contains static sensitive components Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the ...

Страница 4: ... 11 Programming Steps 11 ACU 11 CCS 12 LOC 12 Subsidiary Equipment 13 Programming 13 DCC Participation 13 Local Control 14 Mass Notification Control Settings for the XLS DVC 15 Set the Priority 15 MN Mapping 17 Type IDs 18 Special Function Zones 19 MN Active Tone 19 Fire Active Tone 22 DVC RPU 24 MN Annunciator Programming 25 XLS DVC General Zones 26 OPERATION 26 Mass Notification Events 26 MN Ala...

Страница 5: ...well products Fig 1 to create a system with mass notification capabilities It covers assembling the following key components of a mass notification system Autonomous Control Units ACU Local Operating Consoles LOC Central Control Stations CCS It also details the mass notification MN event priority and describes the system s operation when MN is part of its function The installation and functions co...

Страница 6: ...larms differently from fire alarms Fire alarms are indicated by the Fire Alarm LED and will be counted with the Fire Alarm counter MN alarms are indicated by the Other LED on the display and indicated on an annunciator with a dedicated LED and counted with an OTHER counter MN supervisory events and fire supervisory events share the Supervisory LED piezo sounding pattern and supervisory counter MN ...

Страница 7: ... general paging for prioritization based on site specific requirements A page at the MN level will create a latching MN alarm condition that requires acknowledgment and reset The LOC supports All Call when priority allows LOC pages must be ALL CALL pages MN events can be acknowledged silenced or reset only by an active MN command center When an LOC gains control of acknowledge silence and reset fu...

Страница 8: ... more ACUs in a mass notification system The priority of a CCS will be lower than that of an ACU or LOC in the MN fire system EBI WORKSTATION The EBI workstation displays events and status of the MN and fire systems from any ACU located on an XLS NET It provides two paging levels Level 1 and Level 2 which may be assigned to MN or fire for prioritization based on site specific requirements A page a...

Страница 9: ...vides the audio functions of the CCS It provides three paging levels Level 1 Level 2 and Level 3 which may be assigned to MN fire or general paging for prioritization based on site specific requirements A page at the MN level will create a latching MN alarm condition that requires acknowledgment and reset Multiple CCS locations can be prioritized in hierarchical levels by adjusting the priority le...

Страница 10: ...09A Monitor Module TC809B Mini Monitor Module TC809D Dual Monitor Module or XP10 M Monitor Module can be installed to monitor a UL approved switch or button device installed for initiating MN alarms A Listed UL2017 initiating switch device is required It will generate an MN alarm MN supervisory or MN trouble message when it is programmed with an MN EC type code Fig 8 Monitor Module and Input Devic...

Страница 11: ...To ensure that you are installing and programming the latest features we strongly recommend that you download the most current version of software for each product prior to commissioning any system Contact Technical Support with any questions about software and the appropriate version for a specific application PROGRAMMING Overview When a system is configured for both fire and MN protection progra...

Страница 12: ...input categories and priorities Fig 21 4 Create and program an MN Active Tone page 19 5 Create and program a Fire Active Tone when Fire is the highest priority page 21 ACU Programming Steps XLS3000 XLS NCA2 4 Program with MN type IDs page 18 5 Program with MN Special Function Zones page 19 XLS3000 must be in network display mode to function as part of an ACU XLS DVC 1 Set the MN mode enable paging...

Страница 13: ...articipation In a system with both MN and Fire support DCC must always be disabled for all XLS120s XLS140 2s XLS3000s XLS NCA2s and EBI Workstation XLS3000 XLS NCA2 Panel In the Panel Settings Menu Set DCC Participation to NO to disable DCC Participation Fig 9 Panel Settings Screen 2 XLS3000 Subsidiary Equipment Programming Steps XLS DVC 1 Set the MN Mode Fig 15 2 Set the Associated Node Number fi...

Страница 14: ...S140 2 XLS120 VeriFire Tools In the General II screen Fig 12 VeriFire Tools XLS140 2 XLS120 Leave the Display and Control Center box unchecked in the XLS140 2 and XLS120 service Local Control When the XLS3000 in network display mode or the XLS NCA2 is acting as a subsidiary device that is it is not part of an ACU LOC or CCS its local control setting must be disabled Panel Set Local Mode to NO Fig ...

Страница 15: ... consistent throughout a system XLS3000 XLS NCA2 This field allows the programmer to define the panel s relative fire and MN priority The priority may be set at the panel See Fig 17 or in VeriFire Tools See Fig 18 Panel Navigate through the PanelSettings menu pressing the More softkey until MN PRIORITY OVER FIRE appears Press the softkey next to this selection until the appropriate setting appears...

Страница 16: ...Second button Level 2 always pages Inputs 7 9 or 11 depending on whether the XLS DVC is an ACU LOC or CCS Third button Level 3 always pages Input 13 Input Categories are Fire MN General and MN Active Tone When ACU LOC CCS or Subsidiary is selected as a mode Level 1 inputs default to the MN category and Level 2 inputs default to the Fire category MN Active Tone is a category it is assigned to a seq...

Страница 17: ...prioritize a network XLS DVC over the local XLS DVC reassign the priority for the Network Paging rows to a lower number and therefore a higher priority than that of the Local Paging rows In systems that implement multiple network audio sources the priority of the network sources will be determined by the priority assigned to the active input on the network source For example an XLS DVC that is sen...

Страница 18: ...e Point Characteristics Latchi ng Y yes N no Activate s CBE Device Function ECS MN MONIT OR MN Alarm Y Y Mass Notification alarm monitoring device ECS MN SUPT MN Super visory N Y Indicates tracking supervisory condition ECS MN SUPL MN Super visory Y Y Indicates latching supervisory condition ECS MN TROU BLE MON Troubl e N N Generates a trouble for both short and open circuit conditions Monitor mod...

Страница 19: ...l be suppressed in the panel that made the match Logic equations will be activated ZF21 MN Supervisory Zone Activates for local events when there is an MN supervisory in the system ZF22 MN Trouble Zone MN Trouble Zone Activates for local events when an MN trouble occurs The MN Special Function Zones are available as indicated in Table 11 Table 11 MN Special Function Zone Availability MN Active Ton...

Страница 20: ...mple MN has the highest priority and the MN Active Tone Category has been assigned to Sequence 2 the MN Active Tone It has been assigned a priority of 8 just below the MN Category inputs and above the Fire Category inputs Fig 26 Assign Priority to the MN Active Tone Sequence Create a logic zone that will activate if a ZF20 MN alarm comes in from any MN mapped node 1 Select OR as the function 2 Sel...

Страница 21: ...ig 27 Map the MN Active Tone Sequence to a Logic Zone In the PAM Programming Service add the Logic Zone created in Fig 27 above to the entire MN Active Tone Input row Input 32 Sequence 2 in this example Fig 28 Map the MN Active Tone Sequence to a Logic Zone ...

Страница 22: ... sequences and pages that come below it in priority until a fire reset clears the MN Active Tone NOTE MN or OTHER sequences and pages will not be suppressed for fire alarms without the Fire Active Tone properly prioritized in the PAM In the Audio Message Prog Service of VeriFire Tools DVC programming build the Fire Active Tone audio sequence on the Message Sequences tab Fig 29 Creating a Fire Acti...

Страница 23: ...he Fire Category inputs and above the MN Category inputs Fig 30 Assign Priority to the Fire Active Tone Sequence Map a common general zone for example Z1 to all the PAM points designated as the Fire category 1 Select OR as the function 2 Select Zone Z1 3 Close the equation In this example ZL3 is the Logic Zone programmed for activation of the Fire Active Tone Fig 31 Map the Fire Active Tone Sequen...

Страница 24: ... Add the Fire Active Tone logic equation to fire PAM points DVC RPU SET THE PAGING LEVELS In the COMMON RPU Prog Service screen in DVC programming Select the Paging Levels to enable the ALL CALL buttons in the second column of the DVC KD Addressing DVC RPU address must equal the LCD 160 address See LCD 160 on page 25 Fig 33 Set Paging Levels VeriFire Tools ...

Страница 25: ...CD 160 must be address 5 CAUTION ADDRESSING IS CRITICAL TO COMMAND OPERATIONS THE DVC RPU ADDRESS ON THE DIGITAL AUDIO LOOP MUST EQUAL THE LCD 160 ADDRESS ON THE RDP BUS Fig 35 Block Diagram Illustrating Address Link MN Annunciator Programming DEDICATED MN ALARM ANNUNCIATOR A DVC KD LED annunciator programmed as a dedicated MN alarm annunciator is required for each XLS120 XLS140 2 XLS3000 and XLS ...

Страница 26: ...NCA2 Does not activate the alarm relays Displays MN ALARM in the upper left corner of the display of XLS3000 XLS NCA2 and LCD 160 as well as other information specific to the alarm Activates Special Function Zone ZF20 MN alarm zone Suppresses fire alarms if MN has the highest priority refer to Output Event Suppression on page 29 Activates General Pending type code at the XLS3000 Does not activate ...

Страница 27: ... will not resound Displays MN SUPERVISORY in the upper left corner of the display as well as other information specific to the supervisory message for the XLS3000 XLS NCA2 LCD 160 Is a latching or tracking event based on Type ID see Table 9 The control panel will not return to normal operation until the supervisory condition is corrected and the control panel is reset Resets require two presses of...

Страница 28: ... picked up by participating MN nodes and the MN event will automatically clear from their local systems The EBI Workstation MN and FIRE Reset operation is described in installation instruction 95 8548 MN AND FIRE EVENTS PRESENT IN SYSTEM MN is the highest priority When both MN and fire events are present in the system and MN events have the highest priority press the panel s reset button to Reset ...

Страница 29: ... and Z12 are dedicated fire zones Z2 is an MN alarm zone If Z10 Z11 or Z12 is active and Z2 is not ZL2 will go active If Z10 Z11 or Z12 and Z2 are active ZL2 will go inactive and any outputs mapped to it may be suppressed Outputs All outputs used for MN must be programmed as non silenceable This includes those outputs that are shared between MN and other events such as Fire Dedicated Fire outputs ...

Страница 30: ...it is wired to removing control when the panel does An MN page at an XLS DVC will Give control to its assigned XLS NCA2 or XLS3000 which will maintain its Controls Active LED on and maintain control functions as unblocked Turn off Control Active LEDs and block control functions at all other panels and annunciators An MN page at a DVC RPU will Give control to its assigned LCD 160 which will maintai...

Страница 31: ...mation and Control Solutions office as listed in the phone book or contact a regional office as shown at the end of this document It is recommended that the system test frequency is once per year HONEYWELL IS A REGISTERED TRADEMARK AND ENTERPRISE BUILDINGS INTEGRATOR IS A TRADEMARK OF HONEYWELL INC Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley ...

Отзывы: