HONEYWELL EMERGENCY NOTIFICATION MANAGER
39-00008-1
18
In the XLS140-2 or X L S 1 2 0 Programming Service of
VeriFire Tools, select the Network Mapping screen. Check
the appropriate boxes in the Mass Notification mapping
column.
Fig. 24. MN Mapping, XLS140-2/XLS120
XLS-DVC
XLS-DVC MN mapping consists of:
• Creating a logic equation for the MN Active Tone that will
activate if a ZF20 MN alarm comes in from any MN-
mapped node. Refer page 19 for this programming.
• All Call mapping in VeriFire Tools. MN pages will go out to
the nodes in this map. Refer to the programming section of
the XLS-DVC manual for VeriFire Tools programming.
Type IDs
Program inputs and outputs dedicated to mass notification
with MN Type IDs. Outputs with combined functions may use
other type IDs.
Table 8 lists and describes MN monitor module Type IDs.
Table 8. MN Monitor Type IDs
Type
Code
Point
Type
Point Characteristics
Latchi
ng
(Y=yes
N=no)
Activate
s CBE
Device
Function
ECS/
MN
MONIT
OR
MN
Alarm
Y
Y
Mass
Notification
alarm
monitoring
device
ECS/
MN
SUPT
MN
Super
visory
N
Y
Indicates
tracking
supervisory
condition.
ECS/
MN
SUPL
MN
Super
visory
Y
Y
Indicates
latching
supervisory
condition.
ECS/
MN
TROU
BLE
MON
Troubl
e
N
N
Generates a
trouble for
both short
and open
circuit
conditions.
Monitor module activations with these Type IDs will generate
mass notification events locally and over a network. Trouble
conditions at these points will generate an MN trouble.
Table 9 lists and describes MN control module and panel bell
circuit Type IDs.
Table 9. MN Control Type IDs
Type Code
Point Type
Point Characteristics
Silence able
Switch
Inhibit
Walk
Test
Device Function
MNS GENERAL
NAC
N
N
N
Mass notification
supervised output.
MNS CONTROL
NAC
N
N
N
Mass notification
supervised NAC.
MNS STROBE
NAC
N
N
N
Mass notification
supervised NAC.
MNS SPEAKER
NAC
N
N
N
Mass notification
supervised NAC
for speaker
circuits.
MNS RELAY
Relay
N
N
N
Mass notification
relay output.