HONEYWELL EMERGENCY NOTIFICATION MANAGER
13
39-00008-1
Table 5. CCS Programming Steps
Table 6. Subsidiary Equipment Programming Steps
CCS Programming Steps
XLS-DVC
4
Create and program an MN
Active Tone.
5
Create and program a Fire
Active Tone (when Fire is the
highest priority).
page 21
6
Select FNA node in the All Call
list under General II tab
Subsidiary Equipment
The panels and network annunciators in this section may be
present on an MN network without being part of an ACU, LOC
or CCS. They do not have local control when an MN alarm is
active in the system. They are capable of initiating and
annunciating an MN alarm, but cannot perform acknowledge,
silence, or reset functions while an MN alarm is active in the
system.
Table 6. Subsidiary Equipment Programming Steps
DVC-RPU
MN Paging Levels are not installed when the DVC-RPU acts
as a subsidiary device. Program the DVC-RPU label. Refer to
"DVC-RPU” on page 24.
MN ANNUNCIATOR PROGRAMMING
Program an annunciator as a dedicated MN alarm
annunciator (See page 25). Use XLS-DVC General Zones
Z501 - Z533 to annunciate LOC and ACU paging. Refer to
"XLS-DVC General Zones” on page 26.
Programming
DCC Participation
In a system with both MN and Fire support, DCC must always
be disabled for all XLS120s, XLS140-2s, XLS3000s, XLS-
NCA2s and EBI Workstation.
XLS3000/XLS-NCA2
Panel
: In the Panel Settings Menu:
Set DCC Participation to NO to disable DCC Participation.
Fig. 9. Panel Settings Screen (2), XLS3000
Subsidiary Equipment Programming Steps
XLS-DVC
1
Set the MN Mode**
2
Set the Associated Node
Number field.
3
Program input categories and
priorities.
4
Create and program an MN
Active Tone.
5
Create and program a Fire
Active Tone (when Fire is the
highest priority).
page 21
6
Select FNA node in the All Call
list under General II tab
**MN paging levels are not installed when the XLS-DVC
acts as a subsidiary device.
Subsidiary Equipment Programming Steps
XLS3000*/XLS-NCA2
Field
Refer to
1
Set the mass notification
priority
2
Set the DCC field.
3
Disable Local Control for
XLS3000 in network display
mode, and XLS-NCA2.
4
Map to MN nodes.(Include the
FNA node in the map).
5
Program with MN type IDs.
6
Program with MN Special
Function Zones.
XLS3000 may be in standard or network display mode.
XLS140-2/XLS120
1
Set the mass notification
priority
2
Set the DCC field.
3
Map to MN nodes.
4
Program with MN type IDs.
5
Program with MN Special
Function Zones.