HONEYWELL EMERGENCY NOTIFICATION MANAGER
9
39-00008-1
Fire Network Adapters (FNA). An FNA connects a single
XLS-NET which contains an XLS-DVC and compatible XLS
control units.
The EBI workstation has the capability to acknowledge and
reset events (MN and fire) in the system. MN events can be
acknowledged or reset only by an MNS operator logged into
an active MN command center. Refer to installation instruction
95-8548 for a more detailed description of the EBI Mass
Notification Manager configuration and operation.
Only one EBI workstation may perform paging on a Mass
Notification System at a time.
XLS-NCA2 WITH XLS-DVC
The XLS-NCA2 displays and annunciates fire and MN events
and status for the monitored points in each of the ACUs and
LOCs in the system. It also provides acknowledge, silence,
and reset capabilities. Alarm, supervisory and trouble events
are acknowledged and reset using the same acknowledge
and reset buttons. The reset control resets only the highest
priority active event type in the system. A second reset is
required to reset lower-priority type events. The acknowledge
control block acknowledges all troubles and supervisories for
MN and fire. Fire alarms and MN alarms are acknowledged
one-by-one, based on highest priority events.
The XLS-DVC (in CCS mode) provides the audio functions of
the CCS. It provides three paging levels - Level 1, Level 2 and
Level 3 - which may be assigned to MN, fire, or general paging
for prioritization based on site-specific requirements. A page
at the MN level will create a latching MN alarm condition that
requires acknowledgment and reset. Multiple CCS locations
can be prioritized in hierarchical levels by adjusting the priority
level of the local microphone input. The CCS supports All Call
paging when priority allows. MN pages from a CCS must be
All Call pages. MN events can be acknowledged, silenced or
reset only by an active MN command center.
The following two equipment configurations can meet the
requirements for CCS functionality in an MN system when
combined with MN priority programming:
Configurations
• An EBI workstation with Desktop Microphone Kit.
• An XLS3000 (in network display mode) or XLS-NCA2
combined with an XLS-DVC and its local microphone. For
this combination, a DVC-KD, point must be programmed as
a dedicated visual indicator of an MN alarm.
Fig. 5. CCS Configurations
Refer to "PROGRAMMING” on page 11.
MN Alarm Indicator
A DVC-KD point must be programmed as a dedicated MN alarm indicator for the X L S 1 2 0 , XLS140-2, XLS3000, and XLS-
NCA2. The indicator is not required if a panel is acting as a displayless node.
An EBI workstation does not require an additional annunciator point, as it has a dedicated icon to indicate when an MN alarm is
active . This icon is displayed constantly during an MN alarm.