background image

R7999A,B CONTROLINKS™ CONTROLLER

13

65-0238—10

a

 It is possible that a random external electrical noise has caused a fault checking algorithm to be detected. Resetting the control 

will allow recalculation of the fault and, if it is not a hard failure, the device will continue to operate. If the condition will not clear, 

the device must be replaced.

b

Check ac waveform; severe noise on ac lines can corrupt sampling of ac signals.

c

Verify actuator total resistance and wiper measurements; check the ability of the actuator to travel full stroke using the manual 

override buttons in the actuator. Verify input power to the actuator. if actuator is not functioning, replace the actuator.

d

 Conditional Alarm. Causes the alarm output to be energized, the system may still be operating but requires attention in order to 

modulate or to proceed with the light off sequence. The actuators would be positioned at lightoff point, minimum modulation point 

or maximum modulation point, dependent on what the particular fault is and when the fault is introduced, relative to the R7999 

ControLinks operating state.

Wiring Checkout and Error Faults

The ZM7999 commissioning, a S7999 touchscreen display, or 

other monitoring tools provide an effective means of an indirect 

status reading of all line voltage inputs and outputs. Use these 

tools to confirm wiring. The commissioning tool and monitoring 

tool environments require that a single fuel select input to be 

active before proceeding with communications between the 

tool and controller. Further, simultaneous HF and LF 

commands from the burner are not allowed and will preclude 

communications with the tools. 

The act of bringing actuators successfully “on-line” verifies the 

initial wiring between the controller and actuators. See error 

codes 71 through 74 and/or 54 through 57 for details. Other 

wiring problems occurring between the actuators and 

controller, after commissioning, may be annunciated by fault 

codes 41 through 53 or 61,67,68,69 or 82 through 86.

Burner control wiring interface problems are annunciated by 

fault codes 13, 14, 15, 34, 37.

The Q7999 Universal Subbase is partitioned into a line voltage 

section and a low voltage section. Utilize shielded cabling on 

all low voltage wiring. Keep the earth ground cable shield short 

as possible for all interface wiring as illustrated in Fig. 2.

Replacing an ML Actuator

When the ML7999 Actuator is identified for replacement, you 

should do the following BEFORE the actuator is removed:

1.

Use the ZM software or the S7999 Touchscreen Display 

and make sure the burner configuration has been saved.

2.

Go into the Commission and go to the Actuator that 

needs to be replaced, and Unlock at least one of the 

endpoints.

3.

Remove the wiring and actuator and install the replace-

ment without tightening the setscrews (as described in 

the ML instructions).

4.

You can now go back through the commission procedure 

to set up the new actuator by entering the serial number 

and establish the end points.

5.

Once entered, you can download the existing curve and 

verify the curve firing points.

If the motor had been removed and is now added to the R7999 

system, the R7999 will lockout because the motor serial 

numbers won’t match.

1.

Make sure the system is in “Standby”

2.

Go to the replaced actuator and remove the cover, above 

the wiring about the center of the motor is a Red connec-

tor. Carefully disconnect it.

86

FGR actuator nonresponsive.

Check actuator wiring and stuck damper/valve.

c

 Were the actuators 

commissioned properly–are they set off their mechanical stops?

87

Internal math error (Microprocessor test failed).

Reset control.

a

91

The 4 to 20 mA firing rate input is below 3 mA, Out of Range—Low. 

(Actuators return to or remain at the minimum modulation point with 

the alarm on; the control remains operational only to the extent that 

Minimum Modulation firing operation is allowed.) 

Check CmA+-input (Terminals 39 and 40) for proper operation polarity 

and range. The input must be within 3.0 mA to 21.0 mA. The voltage at 

this terminal must be within 0.7 to 5.0 Vdc, respectively.

Conditional Alarm—Alarm output is energized; controller continues to 

run.

92

The manual potentiometer rate input is higher than an allowable range, 

i.e., Out of Range—High. (The actuators move to the maximum 

modulation point with alarm ON, control will remain operable, yet when 

MANUAL MODE is selected, maximum modulation and alarm output 

shall occur.) Auto mode operation is 

not

 affected.

The Manual potentiometer is out of range high. Make sure a 5000 ohm 

(±10%) potentiometer is being used and wiring to it is correct. 

Shielded cable is recommended.

Conditional Alarm—Alarm output is energized; controller continues to 
run.

d

93

The auxiliary 4-20 mA input must be below 3.0 mA when configured for 

use. (The actuators return or remain at the minimum modulation point 

with alarm ON, the control will remain operable only to the extent that 

Minimum Modulation firing operation is allowed.)

Check XmA+- input (Terminals 37and 38) for proper operation polarity 

and range. The input must be within 3.0 mA to 21.0 mA. The voltage at 

this terminal must be within 0.7 to 5.0 Vdc respectively.

Conditional Alarm—Alarm output is energized; controller continues to 
run.

d

94

After LCO is set by the R7999, the Burner Control must provide a 

Lightoff or Purge request within 20 seconds. (Controller remains in a 

processing demand condition indefinitely waiting for valid inputs on the 

LF, MV and HF inputs; the alarm is sounded after the 20-second period 

expires.)

Check burner control interface wiring and burner control operation 

(Terminals 10, 11, 12). The R7999 is waiting for a command via these 

terminals.

Conditional Alarm—Alarm output is energized; controller continues to 
run.

d

Table 7. Fault Listings and Descriptions. (Continued)

Fault/

Blink 

Code

Description

Corrective Action

Содержание ControLinks R7999A

Страница 1: ...mable behaviors of all actuators during Purge and Standby Programmable behavior of nonselected fuel actuator Independent lightoff and minimum modulation positions Wide power voltage input range 50 60 Hz two models cover global applications Auto Manual input Manual mode firing rate input Pluggable controller to wiring subbase Multipurpose communications port Field configurable device Integrated boi...

Страница 2: ...t Control OUT LCO R7999A 120 Vac 8 0A run 42A inrush UL R7999A 120 Vac 6 0A run 26A inrush CE R7999B 240 Vac 4 0A run 26A inrush CE Alarm ALR R7999A 120 Vac 1A pilot duty UL R7999A 120 Vac 1 0A at PF 0 4 6A inrush CE R7999B 240 Vac 1 0A At PF 0 4 6A inrush CE High Fire HFP R7999A 120 Vac 1A pilot duty UL R7999A 120 Vac 1A at PF 0 4 6A inrush CE R7999B 240 Vac 1A at PF 0 4 6A inrush CE Light Off Po...

Страница 3: ...9 Wiring Subbase There is no direct wiring to the controller Tables 1 and 2 provide the R7999 input and output terminal descriptions respectively Table 3 provides the R7999 maximum field wiring lengths A block hookup diagram for the ML7999 Actuator is shown in Fig 2 and typical wiring diagrams are shown in Fig 4 5 or 6 Earth Ground Earth ground is required for proper operation of the ControLinks s...

Страница 4: ...13 Line voltage input that signals limits are satisfied and that a demand exists to run the burner Provides power to energize Burner Control Voltage present equates to function selected Feedback Air Damper CW S CCW 17 18 19 Provides position feedback for the Air actuator CW Clockwise rotational endpoint of the feedback potentiometer S Variable resistance signal from potentiometer CCW Counterclockw...

Страница 5: ... position 5 Processing Demand State The R7999 enters this state when the LCI has just become active The R7999 makes sure the firing rate command inputs are valid before advancing to the next state 6 Run State The R7999 enters this state when the LCI input is active The high fire or low fire command from the burner control causes the air actuator and the FGR actuator if configured to drive to the p...

Страница 6: ...r wire Make sure that all mechanically tightened joints along the ground path are free of nonconductive coat ings and protected against corrosion on mating surfaces b Follow local and NEC 1 codes cImplies no limitations beyond voltage current times resistance drop considerations versus wire size constraints dRequires ground shield at controller end See Fig 2 4 e Ground shield to digital ground ter...

Страница 7: ...commended as interface wiring If using a USB port a Keyspan or Belkin USB to RS 485 converter is recommended The R7999 requires the presence of one of the Fuel Select inputs to start communications with the ZM7999 ControLinks Commissioning Software Additional wiring interface requirements include that HF and LF command inputs cannot be activated at the same time NOTE A stack gas analyzer is requir...

Страница 8: ...mV 1 1 1 1 1 1 2 3 4 4 3 2 2 GROUND SHIELD TO SUBBASE EARTH GROUND SCREW ON LOW VOLTAGE SIDE OF SUBBASE FUSE LINE VOLTAGE TO CONTROL SYSTEM WITH TYPE SC15 FUSE OR FUSE LIMIT INPUT WITH TYPE SC5 FUSE RS 485 DDL CONNECTOR IS ON R7999 CONTROLLER MUST USE APPROVED FUEL SELECT SWITCH CENTER OFF POSITION NORMALLY OPEN MOMENTARY SWITCH CONNECTION BETWEEN TERMINALS 35 AND 38 MANUAL FIRING RATE POTENTI0MET...

Страница 9: ... VOLTAGE TO CONTROL SYSTEM WITH TYPE SC15 FUSE OR FUSE LIMIT INPUT WITH TYPE SC5 FUSE RS 485 DDL CONNECTOR IS ON R7999 CONTROLLER MUST USE APPROVED FUEL SELECT SWITCH CENTER OFF POSITION NORMALLY OPEN MOMENTARY SWITCH CONNECTION BETWEEN TERMINALS 35 AND 38 MANUAL FIRING RATE POTENTI0METER CONNECTION BETWEEN TERMINALS 36 AND 38 120 VAC RELAY WITH NORMALLY CLOSED CONTACT WIRED INTO LINE FROM 7800 SU...

Страница 10: ...ING RATE POTENTIOMETER CONNECTION BETWEEN TERMINALS 36 AND 38 AN EXTERNAL LINE VOLTAGE 120 VAC RELAY MUST BE ADDED AND WIRED AS SHOWN IN THE ADJACENT PICTURE THE EXTERNAL RELAY IS REQUIRED TO DELAY THE LFP INPUT TO CONTROLINKS SINCE THE FIREYE CONTROL POWERS BOTH THE LFP AND HFP AT THE SAME TIME CONTROLINKS DOES NOT ALLOW THIS CONDITION REMOVE THE LIMIT OPERATING SWITCHES INPUT FROM THE FIREYE TER...

Страница 11: ...lay test failed Reset controla 24 Internal error Time storage Microprocessor test failure Reset control a 25 Internal error Limited move Actuator moving to a position during commissioning mode Reset control a c Check the feedback pot on the actuator indicated by the LED 26 Internal error Targeted move actuator moving to a position but not getting to the postions Reset control a c Can get this if y...

Страница 12: ...r did not go to its commanded position Check for stuck air actuator and or proper shielding on actuator interface Try changing degree of accuracy to 0 5 degree 71 Verifies that the Air actuator accepted the offline online move counter clock wise and move clock wise commands Furthermore all potentiometer tests must be successfully passed to bring an actuator online Check wiring of actuator verify c...

Страница 13: ...s as described in the ML instructions 4 You can now go back through the commission procedure to set up the new actuator by entering the serial number and establish the end points 5 Once entered you can download the existing curve and verify the curve firing points If the motor had been removed and is now added to the R7999 system the R7999 will lockout because the motor serial numbers won t match ...

Страница 14: ...ter command on the Commission screen to enter the pass word You should be into the setup screen If the R7999 Alarms again you may need to repeat the above steps 5 You cannot enter ControLinks commissioning while it is in Alarm 6 Once you have entered the Commission screen return to the replaced actuator and reconnect the Red connec tor 7 Return to the commissioning process by entering the new actu...

Страница 15: ...R7999A B CONTROLINKS CONTROLLER 15 65 0238 10 ...

Страница 16: ...omation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 65 0238 10 M S Rev 02 13 Printed in United States ...

Отзывы: