R7999A,B CONTROLINKS™ CONTROLLER
9
65-0238—10
Fig. 5. Hookup block diagram for Valve Proving System - R7999 and associated equipment.
RS485 DDL
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STACK OR
WATER TEMP.
4-20mA
SSLC
4-20mA
A-1
A-2
CW
S
CCW
F1-1
F1-2
CW
S
CCW
F2-1
F2-2
CW
S
CCW
FG-1
FG-2
CW
S
CCW
RR
XmA+
XmA–
CmA+
CmA–
FUEL 1
AIR
FUEL 2
FGR
MAX
MIN
RESET
(REMOTE)
RS485 DDL
1
2
3
4
5
6
7
8
9
10
11
12
13
14
BURNER
CONTROL
(RM78XX)
CTRL
LIMITS IN
GAS
OIL
ALARM
HFS
LFS
HF
COM
LF
MANUAL FIRING RATE
POTENTIOMETER
5K OHM
L1
(HOT)
L2
GND
AUTO
MANUAL
Q7999
L1
G
L2
A/M
FS1
FS2
ALR
HFP
LFP
HF
MV
LF
LCI
LCO
M34578
MV
FUEL SELECT SWITCH
FUEL 1 mV
FUEL 2 mV
1
1
1
1
1
1
2
3
4
4
3
2
2
GROUND SHIELD TO SUBBASE EARTH GROUND SCREW ON LOW VOLTAGE SIDE OF SUBBASE.
FUSE LINE VOLTAGE TO CONTROL SYSTEM WITH TYPE SC15 FUSE OR FUSE LIMIT INPUT WITH
TYPE SC5 FUSE.
RS-485 DDL CONNECTOR IS ON R7999 CONTROLLER.
MUST USE APPROVED FUEL SELECT SWITCH (CENTER OFF POSITION).
NORMALLY OPEN MOMENTARY SWITCH (CONNECTION BETWEEN TERMINALS 35 AND 38).
MANUAL FIRING RATE POTENTI0METER (CONNECTION BETWEEN TERMINALS 36 AND 38).
120 VAC RELAY, WITH NORMALLY CLOSED CONTACT WIRED INTO LINE FROM 7800 SUBBASE
TERMINAL 9 AND R7999 SUBBASE TERMINAL 11. NOTE: THIS RELAY IS NEEDED FOR VPS
APPLICATION SELECTIONS IF BEFORE, SPLIT, OR BOTH ARE CHOSEN. IT IS NOT REQUIRED
WHEN AFTER IS SELECTED.
AN ADDITION TO THE FUEL CHANGEOVER SWITCH TO ALLOW THE 7800 TO OPERATE THE
VPS FEATURE WHEN FIRING ON GAS AND TO OPERATE THE FUEL VALVES WHEN ON OIL.
L1 L2 G
9
19
18
12
13
15
14
6
17
7
DR1
DR1
DR1
DR1
DR2
DR2
DR2
DR2
CW
CW
CW
CW
S
S
S
S
CCW
CCW
CCW
CCW
RS232
(PC)
RS485
(EXT)
ML7999
ML7999
ML7999
ML7999
1
5
5
MNC
6
6
QM4520
RS232/RS485
CONVERTER
S7999D1048
SYSTEM
DISPLAY
OR
USB TO
RS-485
OR
7
8
7
7
4
8
ILK