Conversion to Modbus RTU
Modbus Communications
7.26.2 Software Configuration
Configure the CGW-MB as a node in the NFN network with a node number.
Refer to the
NOTI•FIRE•NET™ Network Systems Interface Manual (P/N 51584)
or the
High
Speed NOTI•FIRE•NET™ Instruction Manual (P/N 54013)
for details about network
configuration.
When configuring the network, refer to the settings specified in
MB3180 Configuration Settings"
. Settings not specified should be tailored to your network
requirements. Refer to the
MGate MB3000 Modbus CLSS Gateway mainboard User’s
Manual
for details.
1. Connect the MB3180 to a configuration computer through an Ethernet cable as
Figure 7.7: Connect a Configuration Computer
2. Run the
MGate Manager
installation software (
MGM_S
ETUP
_V
ERX
.
X
_B
UILD
_
XXXXXXXX
.
EXE
)
found on the Software CD shipped with the MGate MB3180.
3. Wait for the installation to complete.
4. Run
MGate Manager
.
5. Power up the MB3180.
6. Ensure that the
Ready
and
Ethernet
lights are ON.
7. Configure the MB3180 for the network.
8. Wait for the configuration to complete.
9. Click
OK
.
10.Click
Exit
.
!
CAUTION: ENSURE THAT THE NFN NETWORK CONFIGURATIONS ARE UNCHANGED.
Table 7.36: MGate MB3180 Configuration Settings
Tab
Setting
Mode
RTU Master Mode
Slave ID Map
The MGate MB3180 accepts the Modbus Unit ID as a virtual slave ID and
monitors devices with these virtual slave IDs.
By default, the CGW-MB assigns a Modbus Unit ID to each node on the NFN
network. The ID is equal to node number of the node. They can be changed,
but should be within 1 to 99.
Refer to the
7.16 "To Configure the Modbus Settings"
section for more
information about changing a Modbus Unit ID.